(G) Control parameters
Parameters
5 - 526
Setting of operation time (X13 signal, Pr. 11)
●
Set the time applying the DC injection brake to Pr. 11 "DC injection brake operation time".
●
When the motor does not stop due to large load moment (J), increasing the setting produces an
effect.
●
When Pr. 11 = "0 s", DC injection brake will not operate. (The motor will coast to stop.)
●
When Pr. 11 = "8888", DC injection brake will operate when the X13 signal is turned ON. DC
injection brake will operate when the X13 signal is turned ON even while operating.
●
For the X13 signal input, set "13" in any of Pr. 178 to Pr. 189 to assign the function.
Fig. 5-252:
When Pr. 11 is set to "8888"
I001559E
NOTE
The X13 signal is disabled during PM motor control.
Output fr
equenc
y
[H
z]
DC injection
brake
voltage
Time
ON
Pr. 12
X13
Time
OFF
STF
ON
ON
When Pr. 11 = "8888"