Parameters
(E) Environment setting parameters
FR-F800
5 - 87
PWM carrier frequency automatic reduction function (Pr. 260)
●
Setting Pr. 260 = "1 (initial value)" will enable the PWM carrier frequency auto-reduction function.
If a heavy load is continuously applied while the inverter carrier frequency is set to 3 kHz or higher
(Pr. 72
≥
"3"), the carrier frequency is automatically reduced to prevent occurrence of the inverter
overload trip (electronic thermal O/L relay function) (E.THT). The carrier frequency is reduced to
as low as 2 kHz. (Motor noise increases, but not to the point of failure.)
●
When the PWM carrier frequency automatic reduction function is used, the operation with the
carrier frequency set to 3 kHz or higher (Pr. 72
≥
"3") automatically reduces the carrier frequency
for heavy-load operation as shown below.
.
Pr. 260 setting
Pr. 570 setting
Carrier frequency automatic reduction operation
1
0 (SLD), 1 (LD)
Continuous operation with the 85% or higher rated inverter current
reduces the carrier frequency automatically.
0
0 (SLD)
Continuous operation with the 85% or higher rated inverter current
reduces the carrier frequency automatically.
1 (LD)
Without carrier frequency automatic reduction
(Perform continuous operation with the carrier frequency set to 2 kHz or
lower or with less than 85% of the rated inverter current.)
Tab. 5-42:
Parameter settings for PWM carrier frequency automatic reduction operation
NOTES
Reducing the PWM carrier frequency is effective as a countermeasure against EMI from the
inverter or for reducing leakage current, but doing so increases the motor noise.
When the PWM carrier frequency is set to 1 kHz or lower (Pr. 72
≤
1), the increase in the harmonic
current causes the fast-response current limit to activate before the stall prevention operation,
which may result in torque shortage. In this case, disable the fast-response current limit in Pr. 156
"Stall prevention operation selection".
Parameters referred to
Pr. 156
Stall prevention operation selection
=>
Pr. 570
Multiple rating setting
=>
Pr. 800
Control method selection
=>
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......