Control method
Parameters
5 - 38
5.2.1
Changing the control method
Set the control method.
V/F control, Advanced magnetic flux vector control, and PM motor control are the control methods
available for selection.
When using an IPM motor MM-EFS or MM-THE4, simply performing the IPM parameter initialization
enables the PM motor control.
●
The PM motor test operation can be performed by setting Pr. 800 "Control method selection".
For the FR-F820-02330(55K) or lower, and the FR-F840-01160(55K) or lower.
For the FR-F820-03160(75K) or higher and the FR-F840-01800(75K) or higher.
The initial value differs according to the voltage class. (200V class/400V class)
When the IPM motor MM-EFS or MM-THE4 is selected by Pr. 71 "Applied motor", the rated frequency
of the MM-EFS or MM-THE4 is used. When a PM motor other than the MM-EFS or MM-THE4 is
selected by Pr. 71, 75 Hz (for the motor capacity 15 kW or lower) or 100 Hz (18.5 kW or higher) is used.
Setting the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
●
Motor specifications (the motor capacity and the number of motor poles) must be set to select
Advanced magnetic flux vector control, or PM motor control.
●
Set the motor capacity (kW) in Pr. 80 "Motor capacity" and set the number of motor poles in Pr. 81
"Number of motor poles".
Pr.
Name
Initial
value
Setting range
Description
71
C100
Applied motor
0 to 6, 13 to 16, 20, 23,
24, 40, 43, 44, 50, 53, 54,
70, 73, 74,210, 213, 214,
240, 243, 244, 8090,
8093, 8094, 9090, 9093,
9094
By selecting a standard motor or constant-
torque motor, the thermal characteristic and
motor constant of each motor are set.
80
C101
Motor capacity
9999
0.4 to 55 kW
Set the applied motor capacity.
0 to 3600 kW
9999
V/F control
81
C102
Number of motor poles
9999
2, 4, 6, 8, 10, 12
Set the number of motor poles.
9999
V/F control
83
C104
Rated motor voltage
200/
0 to 1000 V
Set the rated motor voltage (V).
84
C105
Rated motor frequency
9999
10 to 400 Hz
Set the rated motor frequency (Hz).
9999
The setting value of Pr. 3 "Base frequency" is
used.
800
G200
Control method selection
20
9
PM motor test operation (Motor is not driven
even if it is connected.)
20
Normal operation (Motor can be driven.)
NOTE
Setting the number of motor poles in Pr. 81 changes the Pr. 144 "Speed setting switchover" setting
automatically. (Refer to page 5-191.)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......