(D) Operation command and frequency command
Parameters
5 - 140
JOG operation in the External operation
●
Operation can be started and stopped by the start signals (STF and STR signals) when the Jog
operation selection (JOG) signal is ON. (For the operation method, refer to page 4-30.)
●
In the initial setting, the JOG signal is assigned to the terminal JOG.
JOG operation in PU
When the operation panel or the parameter unit is in the JOG operation mode, the motor jogs only
while the start button is pressed.
(For the operation method, refer to page 4-31.)
I002576E
Fig. 5-41:
Jog operation signal timing chart
NOTES
The reference frequency of the acceleration/deceleration time differs according to the Pr. 29
"Acceleration/deceleration pattern selection" setting. (Refer to page 5-104.)
The Pr. 15 setting should be equal to or higher than the Pr. 13 "Starting frequency" setting.
The JOG signal can be assigned to an input terminal by setting Pr. 178 to Pr. 189 (input terminal
function selection). Changing the terminal assignment may affect other functions. Set parameters
after confirming the function of each terminal.
During JOG operation, the second acceleration/deceleration cannot be selected with the RT sig-
nal. (Other second functions are enabled. (Refer to page 5-285.))
When Pr. 79 "Operation mode selection" = "4", JOG operation is started by one push of FWD/REV
key on the operation panel (FR-DU08) and stopped by STOP/RESET key.
This function is invalid when Pr. 79 = "3".
Parameters referred to
Pr. 13
Starting frequency
=>
Pr. 20
Acceleration/deceleration reference frequency
=>
Pr. 21
Acceleration/deceleration time increments
=>
Pr. 29
Acceleration/deceleration pattern selection
=>
Pr. 79
Operation mode selection
=>
Pr. 178 to Pr. 182
(input terminal function selection)
=>
Output
frequency (Hz)
Pr. 15
Pr. 20
setting range
JOG signal
Forward rotation STF
Reverse rotation STR
Forward
rotation
Reverse
rotation
Time
ON
ON
ON
Pr. 16
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......