![Mitsubishi Electric FR-F800 Скачать руководство пользователя страница 396](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884396.webp)
(M) Monitor display and monitor output signal
Parameters
5 - 234
Input MC shutoff signal (Y91)
●
The Fault output 3 (Y91) signal is output when a fault originating in the inverter circuit or a
connection fault occurs.
●
To use the Y91 signal, set "91 (positive logic) or 191 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
●
The following table shows the faults that output the Y91 signal. (For the fault details, refer to page 6-9.)
5.8.7 Output
frequency
detection
The inverter output frequency is detected and output as output signals.
Fault record
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
24 V DC power fault (E.P24)
Operation panel power supply short circuit
RS-485 terminal power supply short circuit (E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault(E.13/E.PBT)
Tab. 5-104:
Faults that lead to Y91 signal output
Parameters referred to
Pr. 13
Starting frequency
=>
Pr. 76
Fault code output selection
=>
Pr.
Name
Initial value
Setting range Description
FM
CA
41
M441
Up-to-frequency
sensitivity
10%
0 to 100%
Set the level where the SU signal turns ON.
42
M442
Output frequency
detection
6 Hz
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON.
43
M443
Output frequency
detection for reverse
rotation
9999
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON in reverse rotation.
9999
Same as the Pr. 42 setting.
50
M444
Second output frequency
detection
30 Hz
0 to 590 Hz
Set the frequency where the FU2 (FB2) signal
turns ON.
870
M400
Speed detection
hysteresis
0 Hz
0 to 5 Hz
Set the hysteresis width for the detected
frequency.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......