32
2. Basic Operation
2.4 Frequently-used parameters (simple mode parameters)
*1
Initial value for the FR-E820-0050(0.75K) or lower, FR-E840-0026(0.75K) or lower, and FR-E820S-0050(0.75K) or lower.
Pr.
Pr.
group
Name
Increment
Initial value
Range
Application
Refer
to
page
Gr.1
Gr.2
0
G000
Torque boost
0.1%
6%
0% to 30%
Set this parameter to obtain a higher starting
torque under V/F control. Also set this when a
loaded motor cannot be driven, the warning
"OL" occurs, and the inverter output is shut off
with the fault indication "E.OC1".
5%
4%
3%
2%
1
H400
Maximum frequency 0.01 Hz
120 Hz
0 to 120 Hz
Set the upper limit for the output frequency.
2
H401
Minimum frequency 0.01 Hz
0 Hz
0 to 120 Hz
Set the lower limit for the output frequency.
3
G001
Base frequency
0.01 Hz
60 Hz
50 Hz
0 to 590 Hz
Set this parameter when the rated motor
frequency is 50 Hz. Check the rating plate of
the motor.
4
D301
Multi-speed setting
(high speed)
0.01 Hz
60 Hz
50 Hz
0 to 590 Hz
Pre-set the speeds that will be switched
among by terminals.
,
,
5
D302
Multi-speed setting
(middle speed)
0.01 Hz
30 Hz
0 to 590 Hz
6
D303
Multi-speed setting
(low speed)
0.01 Hz
10 Hz
0 to 590 Hz
7
F010
Acceleration time
0.1 s
5 s
0 to 3600 s
Set the acceleration time.
8
F011
Deceleration time
0.1 s
5 s
0 to 3600 s
Set the deceleration time.
9
H000
C103
Electronic thermal
O/L relay
0.01 A
Inverter rated
current
0 to 500 A
Protects the motor from heat. Set the rated
motor current.
79
D000
Operation mode
selection
1
0
0 to 4, 6, 7
Select the start and frequency command
sources.
125
T022
Terminal 2
frequency setting
gain frequency
0.01 Hz
60 Hz
50 Hz
0 to 590 Hz
Change the frequency at the maximum
potentiometer setting (5 V in the initial
setting).
,
126
T042
Terminal 4
frequency setting
gain frequency
0.01 Hz
60 Hz
50 Hz
0 to 590 Hz
Change the frequency at the maximum
current input (20 mA in the initial setting).
,
160
E440
User group read
selection
1
0
0, 1, 9999
This function restricts the parameters that are
read by the operation panel and parameter
unit.
313
M410
DO0 output
selection
1
9999
Refer to
.
Set this parameter to assign the functions to
the devices RX9 to RXB for the CC-Link IE
TSN and CC-Link IE Field Network Basic.
314
M411
DO1 output
selection
1
9999
315
M412
DO2 output
selection
1
9999
349
N010
Communication
reset selection
1
0
0, 1
Disable an error reset command given via
communication in the External operation
mode or the PU operation mode.
541
N100
Frequency
command sign
selection
1
0
0, 1
Set this parameter to make the start
command (forward/reverse rotation) inverted
by adding a plus or minus sign to the value of
the frequency command sent through the CC-
Link IE TSN or the CC-Link IE Field Network
Basic.
544
N103
CC-Link extended
setting
1
0
0, 1, 12, 14,
18, 24, 28
Set this parameter to extend the function of
the remote registers for the CC-Link IE TSN or
the CC-Link IE Field Network Basic.
998
E430
PM parameter
initialization
1
0
0, 8009,
8109, 9009,
9109
Select the PM sensorless vector control and
set the parameters that are required to drive a
PM motor.
999
E431
Automatic
parameter setting
1
9999
10, 12, 20,
21, 9999
Changes parameter settings as a batch. The
target parameters include communication
parameters for the Mitsubishi Electric human
machine interface (GOT) connection and the
parameters for the rated frequency settings of
50/60 Hz.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...