Optimal output characteristics (V/F characteristics) for application or load characteristics can be selected.
Application for constant-torque load (Pr.14 ="0", initial value)
• The output voltage will change linearly against the output frequency at the base frequency or lower.
• Set this parameter when driving a load that has constant load torque even when the rotation speed is changed, such as
conveyor, dolly, or roll drive.
Select for constant-torque load (setting value "0") even for fan and pump in the following cases.
• When accelerating a blower with large moment of inertia (J) in a short period of time.
• When it is a constant-torque load such as rotary pump or gear pump.
• When the load torque increases in low speed such as screw pump.
Application for variable-torque load (Pr.14 ="1")
• The output voltage will change in square curve against the output frequency at the base frequency or lower.
• Set this parameter when driving a load with load torque change proportionally against the square of the rotation speed,
such as a fan or pump.
Vertical lift load applications (Pr.14 = "2, 3")
• Set "2" when a vertical lift load is fixed as power driving load at forward rotation and regenerative load at reverse rotation.
•
Pr.0 Torque boost
is valid during forward rotation, and torque boost is automatically changed to "0%" during reverse
rotation.
• Set "3" for an elevated load that is in the driving mode during reverse rotation and in the regenerative load mode during
forward rotation according to the load weight, e.g. counterweight system.
V/F
V/F
V/F
Pr.
Name
Initial value
Setting
range
Description
14
G003
Load pattern selection
0
0
For constant-torque load
1
For variable-torque load
2
For constant-torque lift (boost at reverse rotation: 0%)
3
For constant-torque lift (boost at forward rotation: 0%)
100%
Output voltage
Pr. 3 Base frequency
Output frequency (Hz)
Pr.14
= 0
100%
Output voltage
Pr. 3 Base frequency
Output frequency (Hz)
Pr.14
= 1
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...