8. (E) Environment Setting Parameters
8.16 Inverter parts life display
1
2
3
4
5
6
7
8
9
10
• The remaining life of the main circuit capacitor is calculated from the energization time and the inverter output power (100%
= Start of service life). When the remaining life of the main circuit capacitor falls below 10%, bit 5 of
Pr.255 Life alarm
status display
turns ON and a warning is output by the Y90 signal.
Life display of the relay contacts of terminals A, B, and C (Pr.507)
• The degree of deterioration of the relay contacts of terminals A, B, and C is displayed in
Pr.507
.
• The number of times the contacts of relay turn ON is counted down from 100% (0 time) by 1% (500 times). When the
counter reaches 10% (45,000 times), bit 6 of
Pr.255
turns ON and a warning is output by the Y90 signal.
• Any value can be set in
Pr.507
.
Life display of the inverter module (Pr.509)
• The degree of deterioration of the inverter module is displayed in
Pr.509
.
• The degree of deterioration of the inverter module is determined by the change in the surrounding air temperature of the
module. (The degree is counted down from 100% (no deterioration).) When the remaining life of the inverter module falls
below 15%, bit 8 of
Pr.255
turns ON and a warning is output by the Y90 signal.
Environmental impact diagnosis function (corrosion level display)
(Pr.198)
• The risk of the inverter's corrosive damage (degree of corrosion) can be checked by using a metal corrosion sensor.
• The degree of corrosion is monitored using the metal corrosion sensor (the degree is counted up from level 1). Use
Pr.198
to check the corrosion level. When level 3 is reached, bit 9 of
Pr.255
turns ON and a warning is output by the Y90 signal.
• The following table shows the details of the corrosion level.
*1
Means the remaining service life from when the level is reached. For example, a fault may occur after 4 months if level 3 is reached in a month,
and after 12 years if level 3 is reached in 3 years.
Level
Possibility of
danger
Definition
Remaining design life (estimation)
Warning
output
1
0% to 5%
Corrosion that may affect the inverter is very
unlikely to occur.
—
Not output
2
6% to 24%
Corrosion that may affect the inverter is likely to
occur. Users should improve the environment
(by a filter or ventilation).
Corrosive damage may cause faults of the
inverter in a period 16 times as long as the
service life so far.
Not output
3
25% to 100%
Corrosion that may affect the inverter is very
likely to occur. Users should improve the
environment (by a filter or ventilation). Consider
replacing the inverter early as required.
Corrosive damage may cause faults of the
inverter in a period 4 times as long as the
service life so far.
Output
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...