12. (M) Item and Output Signal for Monitoring
12.1 Speed indication and its setting change to rotations per minute
• To display the machine speed, set
Pr.37
to the value which corresponds to the speed of machine operated at the frequency
set in
Pr.505
.
For example, when
Pr.505
is set to 60 Hz and
Pr.37
is set to "1000", the operation panel indicates "1000" as the monitor
value of machine speed while the output frequency is 60 Hz. "500" is displayed while the output frequency is 30 Hz.
• The operation panel indicates the upper 4 digits when the rotation speed or machine speed is displayed. For example,
when the internal value "1770.950" is monitored, the operation panel indicates "1770".
*1
Motor speed r/min conversion formula: frequency × 120 / number of motor poles (
Pr.81
or
Pr.454
)
Machine speed conversion formula:
Pr.37
× frequency /
Pr.505
The item set in
Pr.505
is consistently a frequency (Hz).
When
Pr.81 (Pr.454)
= "9999", the number of motor poles is regarded as 4.
NOTE
• The inverter's output frequency is displayed as synchronous speed under V/F control. The displayed value is "actual motor
speed" + "motor slip". When Advanced magnetic flux vector control, Real sensorless vector control, or PM sensorless vector
control is selected, the actual motor speed (estimated value by motor slip calculation) is used. When the encoder feedback
control or Vector control is selected, the actual motor speed from the encoder is used.
• To change the main monitor of the operation panel (operation panel main display), refer to
Pr.52
.
• Since the panel display of the operation panel is in 4 digits, the monitor value of more than "9999" is displayed as "----". Display
the frequency on the operation panel when a value equal to or more than 10000 r/min needs to be monitored or set.
• The displayed machine speed is the value converted from the frequency. Therefore, the setting value and read value may
fluctuate due to rounding during the conversion.
• When the FR-A8ND is connected, the frequency display (setting) is used regardless of the
Pr.53
setting.
Parameters referred to
Pr.1 Maximum frequency
Pr.52 Operation panel main monitor selection
Pr.81 Number of motor poles
Pr.800 Control method selection
Pr.53 setting
Output frequency
indication
Set frequency
indication
Running speed
indication
Frequency setting
Parameter setting
0 (initial value) 0.01 Hz
0.01 Hz
1 r/min
0.01 Hz
0.01 Hz
1
1 r/min
1 r/min
1 r/min
1 r/min
1 r/min
4
0.001 (machine
speed
)
0.001 (machine
speed
1 (machine speed
)
0.001 (machine
speed
0.01 Hz
CAUTION
• Make sure to set the running speed and the number of motor poles.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...