396
15. (A) Application Parameters
15.6 Dancer control
15.6
Dancer control
PID control is performed using detected dancer roll position as feedback data. The dancer roll is controlled to be at a designated
position.
*1
Initial value for the FR-E820-0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or lower, and FR-E820S-0110(2.2K) or
lower.
*2
Initial value for the FR-E820-0240(5.5K) or higher, FR-E840-0120(5.5K) or higher, and FR-E860-0090(5.5K) or higher.
Pr.
Name
Initial value Setting range
Description
44
F020
Second acceleration/
deceleration time
0 to 3600 s
Set the acceleration/deceleration time during dancer control.
In dancer control, this parameter becomes the acceleration/deceleration
time of the main speed.
This setting does not operate as the second acceleration/deceleration time.
10 s
45
F021
Second deceleration
time
9999
0 to 3600 s
Set the deceleration time during dancer control.
In dancer control, this parameter becomes the deceleration time of the
main speed.
This setting does not operate as the second deceleration time.
9999
Pr.44
is the deceleration time.
128
A610
PID action selection
0
0
No PID action
40
PID reverse action
Additive method: Fixed
For dancer control
41
PID forward action
Additive method: Fixed
42
PID reverse action
Additive method: Ratio
43
PID forward action
Additive method: Ratio
Others
Refer to
.
129
A613
PID proportional band
100%
0.1% to
1000%
If a narrow proportional band is set (small parameter setting value), the
manipulated amount changes considerably by slight changes in the
measured value.
As a result, response improves as the proportional band becomes
narrower, though stability worsens as shown by the occurrence of hunting.
Gain Kp=1/proportional band
9999
No proportional control
130
A614
PID integral time
1 s
0.1 to 3600 s
With deviation step input, this is the time (Ti) used for obtaining the same
manipulated amount as proportional band (P) by only integral (I) action.
Arrival to the set point becomes quicker the shorter an integral time is set,
though hunting is more likely to occur.
9999
No integral control
131
A601
PID upper limit
9999
0% to 100%
Set the upper limit.
The FUP signal is output when the feedback value exceeds this setting.
The maximum input (20 mA/5 V/10 V) of the measured value (terminal 4)
is equivalent to 100%.
9999
No function
132
A602
PID lower limit
9999
0% to 100%
Set the lower limit.
The FDN signal is output when the measured value (terminal 4) falls below
the setting range.
The maximum input (20 mA/5 V/10 V) of the measured value is equivalent
to 100%.
9999
No function
133
A611
PID action set point
9999
0% to 100%
Set the set point during PID control.
9999
Input of set point by terminal selected by
Pr.609
134
A615
PID differential time
9999
0.01 to 10 s
With deviation ramp input, this is the time (Td) used for obtaining the
manipulated amount only by proportional action (P).
Response to changes in deviation increase greatly as the differential time
increases.
9999
No differential control
609
A624
PID set point/deviation
input selection
2
2
The set point is input through terminal 2.
3
The set point is input through terminal 4.
4
The set point is input via communication
5
The set point is input by the PLC function.
610
A625
PID measured value
input selection
3
2
The measured value is input through terminal 2.
3
The measured value is input through terminal 4.
4
The measured value is input via communication.
5
The measured value is input by the PLC function.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...