15. (A) Application Parameters
15.2 Stop-on-contact control
Setting the stop-on-contact control
• Make sure that the inverter is in External or Network operation mode. (Refer to
• Select either Real sensorless vector control (speed control) or Advanced magnetic flux vector control.
• Set "1 or 11" in
Pr.270 Stop-on-contact control selection
.
• Set the output frequency for stop-on-contact control in
Pr.6 Multi-speed setting (low speed)
.
Set the frequency as low as possible (about 2 Hz). If a frequency higher than 30 Hz is set, it operates with 30 Hz.
• When both the RT and RL signals are switched ON, the inverter enters the stop-on-contact control, and operation is
performed at the frequency set in
Pr.6
independently of the preceding speed.
• Setting
Pr.270
= "11" disables stall prevention stop (E.OLT) during stop-on-contact control (with both RL and RT signals
ON).
NOTE
• By increasing the
Pr.275
setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OC[]) may occur
or the machine may oscillate in stop-on-contact status.
• The stop-on-contact function is different from the servo-lock function, and if used to stop or hold a load for an extended period,
this function can cause the motor to overheat. After a stop, immediately switch to a mechanical brake to hold the load.
• Under the following operating conditions, the stop-on-contact function is invalid:
PU operation (
Pr.79
), JOG operation (JOG signal), PU + External operation (
Pr.79
), PID control function operation (
Pr.128
),
Remote setting function operation (
Pr.59
), Automatic acceleration/deceleration operation (
Pr.292
), Start time tuning
Function switching of stop-on-contact control selection
Set frequency and validity of the stop-on-contact control (Pr.270 = "1 or
11")
• The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected together.
• Stop-on-contact control is disabled when remote setting function is selected (
Pr.59
= 1 to 3).
Main functions
Normal operation (Either RL or RT is OFF or both
are OFF.)
Stop-on-contact control (Both RL and RT are ON.)
Real sensorless vector
control
Advanced magnetic flux
vector control
Real sensorless vector
control
Advanced magnetic flux
vector control
Output frequency
Multi-speed, 0 to 5 V, 0 to 10 V, 4 to 20 mA, etc.
Pr.6
setting
Stall prevention operation
level
—
Pr.22
setting
—
The smaller value set in
either
Pr.22
or
Pr.48
Torque limit level
Pr.22
setting
—
Pr.22
setting
—
Excitation current low-speed
scaling factor
—
The current is compensated by
Pr.275
(0% to 300%)
setting from normal operation.
Carrier frequency
Pr.72
setting
When output frequency is 3 Hz or lower,
Pr.276
setting (
Pr.72
when
Pr.276
= "9999")
Fast-response current limit
—
Enabled
—
Disabled
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...