8. (E) Environment Setting Parameters
8.10 Parameter write selection
*2
Writing during operation is disabled. To change the parameter setting value, stop the operation.
Parameter write disabled (Pr.77 = "1")
• Parameter write, Parameter clear, and All parameter clear are disabled. (Parameter read is enabled.)
• The following parameters can be written even if
Pr.77
= "1".
*1
Writing during operation is disabled. To change the parameter setting value, stop the operation.
Parameter write enabled during operation (Pr.77 = "2")
• These parameters can always be written.
• The following parameters cannot be written during operation even if
Pr.77
= "2". To change the parameter setting value,
stop the operation.
Pr.
Name
Pr.
Name
22
Stall prevention operation level
297
Password lock/unlock
75
Reset selection/Disconnected PU detection/PU stop
selection
496, 497
(Remote output)
77
Parameter write selection
805
Torque command value (RAM)
79
Operation mode selection
806
Torque command value (RAM, EEPROM)
160
User group read selection
997
Fault initiation
296
Password lock level
1020
Trace operation selection
Pr.
Name
Pr.
Name
23
Stall prevention operation level compensation
factor at double speed
455
Second motor excitation current
40
RUN key rotation direction selection
456
Rated second motor voltage
48
Second stall prevention operation level
457
Rated second motor frequency
60
Energy saving control selection
458 to 462
(Second motor constant)
61
Reference current
463
Second motor auto tuning setting/status
66
Stall prevention operation reduction starting
frequency
507
Display ABC relay contact life
71
Applied motor
541
Frequency command sign selection
79
Operation mode selection
560
Second frequency search gain
80
Motor capacity
570
Multiple rating setting
81
Number of motor poles
574
Second motor online auto tuning
82
Motor excitation current
631
Inverter output fault detection enable/disable
selection
83
Rated motor voltage
639, 640
(Brake sequence)
84
Rated motor frequency
673
SF-PR slip amount adjustment operation
selection
90 to 94
(Motor constant)
699
Input terminal filter
95
Online auto tuning selection
702
Maximum motor frequency
96
Auto tuning setting/status
706, 707, 711,
712, 717, 721,
724, 725, 1412
(PM motor tuning)
178 to 196
(Input and output terminal function selection)
720, 737
(Motor starting resistance tuning
compensation coefficient 2)
261
Power failure stop selection
738 to 746, 1413
(Second PM motor tuning)
277
Stall prevention operation current switchover
800
Control method selection
289
Inverter output terminal filter
858
Terminal 4 function assignment
292
Automatic acceleration/deceleration
859
Torque current/Rated PM motor current
293
Acceleration/deceleration separate selection
860
Second motor torque current/Rated PM motor
current
298
Frequency search gain
998
PM parameter initialization
313 to 322
(Extended output terminal function selection)
999
Automatic parameter setting
329
Digital input unit selection
1002
Lq tuning target current adjustment coefficient
415
Inverter operation lock mode setting
418
Extension output terminal filter
450
Second applied motor
451
Second motor control method selection
453
Second motor capacity
454
Number of second motor poles
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...