15. (A) Application Parameters
15.6 Dancer control
NOTE
• After changing the
Pr.267
setting, check the voltage/current selection switch. Incorrect setting may cause a fault, failure or
malfunction. (Refer to
for the setting.)
• If the Multi-speed operation (RH, RM, RL, or REX) signal, or JOG signal is input during regular PID control, PID control is
interrupted. However, at dancer control, these signals are treated as main speed commands, so PID control is continued.
• During dancer control,
Pr.44 and Pr.45
(Second acceleration/deceleration time) is the parameter for setting the acceleration/
deceleration time for the main speed command. This function does not work as a second function.
• When the switchover mode is set by setting "6" to
Pr.79
, dancer control (PID control) is invalid.
• The acceleration/deceleration action of the main speed command is the same as that when the frequency is increased or
decrease by analog input. The SU signal sometimes stays ON even if operation is turned ON/OFF by the start signal. The set
frequency monitor is the value "main speed c PID control" which is constantly changing.
• With the main speed setting frequency setting, acceleration/deceleration is performed for the acceleration/deceleration time
set in
Pr.44
and
Pr.45
, and with the output frequency setting, acceleration/deceleration is performed for the acceleration/
deceleration time set in
Pr.7
and
Pr.8
. For this reason, with the output frequency, when the time set in
Pr.7
and
Pr.8
is longer
than the time set in
Pr.44
and
Pr.45
, acceleration/deceleration is performed for the acceleration/deceleration time set in
Pr.7
and
Pr.8
.
• The limit of the integral term is the smaller of 100% and the value after conversion of the straight line after interpolation of
Pr.1
Maximum frequency
by
C2 (Pr.902)
and
Pr.125
to the PID manipulated amount.
However, note that the lower limit frequency limits the output frequency, but does not restrict the action of the integral item.
Parameters referred to
Pr.57 Restart coasting time
Pr.59 Remote function selection
Pr.73 Analog input selection
Pr.79 Operation mode selection
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gain
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...