8. (E) Environment Setting Parameters
8.18 Current average value monitor signal
Pr.555 Current average time setting
• The output current average is calculated during start pulse (1 second) HIGH output. Set the time for calculating the average
current during start pulse output in
Pr.555
.
Pr.557 Current average value monitor signal output reference current
setting
Set the reference (100%) for outputting the output current average value signal. The signal output time is calculated with the
following formula.
The output time range is 0.5 to 9 seconds. When the output current average value is less than 10% of the setting value in
Pr.557
, the output time is 0.5 second, and when it is more than 180%, the output time is 9 seconds.
For example, when
Pr.557
= 10 A and the output current average value is 15 A:
15 A/10 A × 5 s = 7.5 s, thus the Current average monitor signal maintains LOW output for 7.5 seconds.
Pr.503 Maintenance timer output
After LOW output of the output current value is performed, HIGH output of the maintenance timer value is performed. The
maintenance timer value output time is calculated with the following formula.
The output time range is 2 to 9 seconds. When
Pr.503
is less than 16000 hours, the output time is 2 seconds. When it is more
than 72000 hours, the output time is 9 seconds.
Output current average value
× 5 s
(Output current average value 100%/5 s)
Pr.557
setting value
9
0.5
10
(%)
(s)
Output current average value
180
Signal output time
Pr.503
× 100
× 5 s
(Maintenance timer value 100%/5 s)
40000h
9
2
16000
(h)
(s)
Maintenance timer value
72000
Signal output time
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...