163
8. (E) Environment Setting Parameters
8.2 Reset selection / disconnected PU detection / PU stop selection
1
2
3
4
5
6
7
8
9
10
2.
Press the PU/EXT key three times (the PS warning is reset)
when
Pr.79 Operation mode selection
= "0" (initial value) or "6".
When
Pr.79
= "2, 3, or 7", the PU stop warning can be cleared with one keystroke.
• The inverter can be restarted by performing the reset operation (by turning OFF and ON the power or inputting the RES
signal).
NOTE
• Even when
Pr.250 Stop selection
≠
"9999" is set and coasting stop is selected, using the PU stop function in the External
operation mode does not provide coasting stop but deceleration stop.
Reset limit (P.E107) (for the safety communication model only)
• When "10" is set in
P.E107
or any value from "10000 to 10003, 10014 to 10017" is set in
Pr.75
, the reset command input
(using the STOP/RESET key or the RES signal) is disabled when the protective function (E.SAF) is activated. Turn ON the
power supply of the inverter again to reset the inverter.
NOTE
• When a communication option is installed, reset is enabled when the protective function (E.SAF) is activated regardless of
P.E107
or
Pr.75
setting.
Parameters referred to
Pr.79 Operation mode selection
Pr.250 Stop selection
Pr.551 PU mode operation command source selection
Speed
Time
Key
Key
Stop/restart example for External operation
Operation
panel
STF ON
(STR) OFF
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which
is dangerous.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...