15.1 Brake sequence function
NOTE
• During deceleration, inverter output is shut OFF when the frequency reaches
Pr.13 Starting frequency
or 0.5 Hz, whichever
is lower. For
Pr.278 Brake opening frequency
, set a frequency equal to or higher than the
Pr.13
setting or 0.5 Hz.
•
Pr.285 Overspeed detection frequency
is valid under encoder feedback control (used with the Vector control compatible
option) even if a value other than "7 or 8" is set in
Pr.292 Automatic acceleration/deceleration
.
• Setting
Pr.278
too high activates the stall prevention and may cause E.MB4.
• E.MB4 occurs when the time period calculated by adding
Pr.280
to the acceleration time from
Pr.13
to
Pr.278
reaches or
exceeds 2 seconds.
Parameters referred to
Pr.13 Starting frequency
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
ON
Time
Output
frequency
(Hz)
Less than 2s
Output frequency (Hz)
Pr.278
Pr.13
Brake opening request
(BOF signal)
Pr.280
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...