10. (D) Operation Command and Frequency Command
10.1 Operation mode selection
• When parameter changing is seldom necessary, setting "2" fixes the operation mode to the External operation mode.
When frequent parameter changing is necessary, setting "0" (initial value) allows the operation mode to be changed easily
to the PU operation mode by pressing the PU/EXT key on the operation panel. After switching to the PU operation mode,
always return to the External operation mode.
• The STF or STR signal is used as a start command. The input voltage or current via terminal 2 or 4, multi-speed setting
signal, or JOG signal is used as a frequency command.
PU operation mode (Pr.79 = "1")
• Select the PU operation mode when giving start and frequency commands by only the key operation of the operation panel.
• When
Pr.79
="1", the inverter starts up in the PU operation mode at power-ON. The mode cannot be changed to other
operation modes.
• When the PU operation mode is selected, the PU operation mode (PU) signal can be output.
For the terminal used for the PU signal, set "10" (positive logic) or "110" (negative logic) in any parameter from
Pr.190 to
Pr.196 (Output terminal function selection)
.
PU/External combined operation mode 1 (Pr.79 = "3")
• Select the PU/External combined operation mode 1 when giving a frequency command from the operation panel and giving
a start command with the external start switches.
• Set "3" in
Pr.79
. The mode cannot be changed to other operation modes.
• When the frequency commands are given using the multi-speed setting signals (external signals), they have a higher
priority than the frequency commands given from the PU. When the AU signal is ON, inputting the command signals via
terminal 4 is enabled.
PU/External combined operation mode 2 (Pr.79 = "4")
• Select the PU/External combined operation mode 2 when giving a frequency command from the external potentiometer,
or multi-speed and JOG signals, and giving a start command by key operation of the operation panel.
Inverter
Frequency setting
potentiometer
5
10
2
Forward rotation start
Reverse rotation start
STF
STR
SD
Switch
Potentiometer
Operation panel
Operation panel
Inverter
SD
STF
STR
Forward rotation
start
Reverse rotation
start
Switch
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...