104
4. Control Method
4.4 Selecting the PM sensorless vector control
4.4
Selecting the PM sensorless vector control
Initializing the parameters required for the PM sensorless vector control
(Pr.998)
• Use PM parameter initialization to set the parameters required for driving a PM motor.
• Perform offline auto tuning before setting Pr.998. (Refer to
.)
• All the parameters required for PM motor control are automatically set by setting
Pr.998
≠
"0".
• To use a motor capacity that is one rank lower than the inverter capacity, set
Pr.80 Motor capacity
before performing PM
parameter initialization.
• When "8009 or 9009" is set in
Pr.998
, the motor speed which was set/monitored in frequencies is set/monitored in motor
rotations per minute. To use frequency to display or set, set
Pr.998
= "8109 or 9109".
• Set
Pr.998
= "0" to change the PM sensorless vector control parameter settings to the parameter settings required to drive
an induction motor.
NOTE
• Make sure to set
Pr.998
before setting other parameters. If the
Pr.998
setting is changed after setting other parameters, some
of those parameters are initialized too. (Refer to the "List of the target parameters for the motor parameter initialization".)
• To change back to the parameter settings required to drive an induction motor, perform Parameter clear or All parameter clear.
• If the setting of
Pr.998 PM parameter initialization
is changed from "8009 or 9009 (rotations per minute)" to "8109 or 9109
(frequency)", all the relevant parameters are initialized.
The purpose of Pr.998 is not to change the display units. Use
Pr.53 Frequency / rotation speed unit switchover
to change
the display units between rotations per minute and frequency. Using
Pr.53
enables switching the unit between rotations per
minute and frequencies without initializing the setting of the motor parameters.
• The PM parameter initialization (
Pr.998
) changes parameter settings for the first motor. When a PM motor is used as the
second motor, parameters for the second motor must be set individually.
List of the target parameters for the motor parameter initialization
• The settings of the parameters in the following table are changed to the settings for PM sensorless vector control by
performing the motor parameter initialization using
Pr.998 PM parameter initialization
. The changed settings differ
according to the specification (capacity) of the PM motor used.
PM
PM
PM
Pr.
Name
Initial
value
Setting
range
Description
998
E430
PM parameter
initialization
0
0
Parameter setting (in frequencies) for an
induction motor
The setting of the motor parameters is
changed to the setting required to drive an
induction motor.
8009
Parameter setting (in rotations per minute)
for an IPM motor (after tuning)
The setting of the motor parameters is
changed to the setting required to drive an
IPM motor. (Set
Pr.71 Applied motor
and perform offline auto tuning in
advance. (Refer to
8109
Parameter setting (in frequencies) for an
IPM motor (after tuning)
9009
Parameter setting (in rotations per minute)
for an SPM motor (after tuning)
The setting of the motor parameters is
changed to the setting required to drive an
SPM motor. (Set
Pr.71 Applied motor
and perform offline auto tuning in
advance. (Refer to
9109
Parameter setting (in frequencies) for an
SPM motor (after tuning)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...