116
5. Speed Control
5.4 Setting the torque limit level
• To set individually for each quadrant, use
Pr.812 Torque limit level (regeneration), Pr.813 Torque limit level (3rd
quadrant), Pr.814 Torque limit level (4th quadrant)
. When "9999" is set,
Pr.22
setting is regarded as torque limit level
in all the quadrants.
Torque limit level using analog input (terminal 4) (Pr.810 = "1", Pr.858)
• The torque is limited with the analog input of terminal 4. (External torque limit)
• Torque limit using analog input is valid with a limit value lower than the internal torque limit
(Pr.22, Pr.812 to Pr.814)
. (If
the torque limit using analog input exceeds the internal torque limit, the internal torque limit is valid.)
• For inputting from terminal 4, set
Pr.858 Terminal 4 function assignment
= "4".
• The torque limit using analog input can be calibrated by the calibration parameters
C38 (Pr.932) to C41 (Pr.933)
. (Refer
.)
Internal torque limit 2 (Pr.810 = "2", Pr.805, Pr.806)
• The setting value of
Pr.805
or
Pr.806
is used as the torque limit value.
• When the CC-Link, CC-Link IE TSN, or CC-Link IE Field Network is used, the torque limit value can be input using a remote
register (RWwC).
*1
The torque limit setting is defined as an absolute value.
*2
The torque limit value can also be set using the operation panel or parameter unit.
*3
The torque can also be limited by setting a value in
Pr.805
or
Pr.806
.
*4
On the operation panel or parameter unit, the setting range is "673 to 1327 (-327% to 327%)" and the setting increment is 1%.
quad1
(Pr.22)
quad4
(Pr.814)
(Pr.813)
quad2
(Pr.812)
Reverse
rotation
Forward
rotation
Torque limit
Speed
Reverse
driving
Reverse
regeneration
Rated speed
quad3
+
-
Forward
regeneration
Forward
driving
Calibration example of terminal 4
400
150
0
Torque setting signal
100%
Bias
0
20mA
C40(Pr.933)
Gain
C38(Pr.932)
C39(Pr.932)
C41(Pr.933)
T
orque(%)
Initial value
Pr.804
setting
Torque limit input
Setting range
Setting increments
Required condition
1
Torque limit by
Pr.805
,
Pr.806
600 to 1400
(-400% to 400%)
1%
—
3
Torque limit by remote register (RWwC)
FR-A8NC is installed, or CC-Link
IE TSN or CC-Link IE Field
Network Basic is used.
5
Torque limit by remote register (RWwC)
-32768 to 32767 (two's
complement)
(-327.68% to 327.67%)
0.01%
6
Torque limit by
Pr.805
,
Pr.806
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...