15. (A) Application Parameters
15.7 Automatic restart after instantaneous power failure / flying start with an induction motor
Restart at every start (Pr.162 = "10 or 11")
• When "10 or 11" is set in
Pr.162
, a restart operation is performed at each start and automatic restart after instantaneous
power failure (after the time period set in
Pr.57
elapsed). When "0 (initial value) or 1" is set in
Pr.162
, a restart operation
is performed at the first start after a power-ON, and from the second power-ON onwards, a start from the starting frequency
is performed.
Automatic restart operation of the MRS (X10) signal
• The restart operation after restoration from output shutoff by the MRS (X10) signal is as shown in the following table
according to the
Pr.30
setting.
NOTE
• When output is shut off using safety stop function (terminals S1 and S2), the inverter restarts in the same way as when output
is shut off by the MRS (X10) signal.
• Operation is selectable as shown in the table above when
Pr.162 Automatic restart after instantaneous power failure
selection
= "0 or 1". When
Pr.162 Automatic restart after instantaneous power failure selection
= "10 or 11" (automatic
restart operation at each start), a restart operation is performed regardless of the setting of
Pr.30 Regenerative function
selection
.
• Set "24" in any parameter from
Pr.178 to Pr.189 (Input terminal function selection)
to assign the output stop (MRS) signal
to the input terminal, and "10" to assign the Inverter operation enable (X10) signal.
Adjustment of restart coasting time (Pr.57)
• Restart coasting time is the time period from the occurrence of instantaneous power failure until the operation is restarted
after power is restored.
With frequency search, the motor speed is detected and operation is restarted after the coasting time.
• To enable restart operation, set "0" to
Pr.57 Restart coasting time
. If "0" is set to
Pr.57
, the coasting time is automatically
set to the following number of seconds. Generally, this setting does not interfere with inverter operation.
• Inverter operation is sometimes hindered by the size of the moment of inertia (J) of the load, output frequency, or the
residual magnetic flux in the motor. Adjust this coasting time within the range 0.1 to 30 seconds to match the load
specification.
Pr.30 setting
Operation after restoration from output shutoff by the MRS (X10) signal
2
Restart operation (starting from the coasting speed)
Other than the above
Starting from
Pr.13 Starting frequency
.
Voltage
class
Inverter
Coasting time (s)
ND
LD
200 V
FR-E820-0080(1.5K) or lower
FR-E820S-0080(1.5K) o lower
FR-E820-0050(0.75K) or lower
FR-E820S-0050(0.75K) or lower
1
FR-E820-0110(2.2K) or higher
FR-E820S-0110(2.2K)
FR-E820-0080(1.5K) or higher
FR-E820S-0080(1.5K) or higher
2
400 V
FR-E840-0040(1.5K) or lower
FR-E840-0026(0.75K) or lower
1
FR-E840-0060(2.2K) or higher
FR-E840-0040(1.5K) or higher
2
575 V
FR-E860-0027(1.5K) or lower
FR-E860-0017(0.75K)
0.5
FR-E860-0040(2.2K) or higher
FR-E860-0027(1.5K) or higher
1
Instantaneous power failure
(interruption) time
Coasting time
Pr.57
setting
Power supply
(R/L1
、
S/L2
、
T/L3)
Inverter output
frequency f (Hz)
Interruption ≤
Pr.57
setting
Interruption >
Pr.57
setting
Instantaneous power failure
(interruption) time
Coasting time
Pr.57
setting
Power supply
(R/L1
、
S/L2
、
T/L3)
Inverter output
frequency f (Hz)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...