12. (M) Item and Output Signal for Monitoring
12.4 Adjustment of terminal FM and terminal AM
12.4
Adjustment of terminal FM and terminal AM
By using the operation panel, you can adjust (calibrate) terminal FM and terminal AM to full-scale deflection.
*1
On the LCD operation panel used as the command source, the parameter number in parentheses appears instead of that starting with the letter C.
*2
The setting is available only for the FR-E800-1.
*3
The setting is available only for the FR-E800-4 and FR-E800-5.
Terminal FM calibration (C0 (Pr.900)) (FM type only)
• The output via terminal FM is set to the pulse output. By setting
C0 (Pr.900)
, the meter connected to the inverter can be
calibrated by parameter setting without use of a calibration resistor.
• The pulse train output via terminal FM can be used for digital display on a digital counter. The output is 1440 pulses/s at
full scale. (Refer to
for the full-scale value of each monitor item.)
*1
Not required when calibrating with operation panel.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, perform calibration using
the operation panel.
*2
In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
• Calibrate the output via terminal FM in the following procedure.
1.
Connect an indicator (frequency meter) across terminals FM and SD on the inverter. (Note the polarity. Terminal FM
is positive.)
2.
When a calibration resistor has already been connected, adjust the resistance to "0" or remove the resistor.
3.
Set a monitor item in
Pr.54 FM terminal function selection
When the output frequency or inverter output current is selected on the monitor, set the output frequency or current
value at which the output signal will be 1440 pulses/s, using
Pr.55 Frequency monitoring reference
or
Pr.56
Current monitoring reference
beforehand. Normally, at 1440 pulses/s the meter deflects to full-scale.
4.
If the meter needle does not point to maximum even at maximum output, calibrate it with
C0 (Pr.900)
.
Pr.
Name
Initial value Setting range
Description
C0 (900)
M310
FM terminal calibration
—
—
Calibrates the scale of the meter connected to terminal FM.
C1 (901)
M320
AM terminal calibration
—
—
Calibrates the scale of the analog meter connected to terminal
AM.
867
M321
AM output filter
0.01 s
0 to 5 s
Set a filter for output via terminal AM.
1200
M390
AM output offset calibration
3000
2700 to 3300
Calibrates the scale of the meter when the analog output is 0.
8VDC
T2
T1
Pulse width T1: Adjust using calibration parameter
C0
Pulse cycle T2: Set with
Pr.55
(frequency monitor)
Set with
Pr.56
(current monitor)
(Digital indicator)
(-)
1440 pulses/s(+)
FM
SD
Indicator
1mA full-scale
analog meter
(+)
1mA
FM
SD
Calibration
resistor
*1
(-)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...