11
12
13
14
15
16
17
18
19
20
281
12. (M) Item and Output Signal for Monitoring
12.3 Monitor display selection for terminals FM and AM
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the current value
(for example, 60 Hz or 120 Hz) at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal
5. Output voltage is proportional to the frequency. (The maximum output voltage is 10 VDC.)
*1
Differs depending on the parameter initial value group. (60/50 Hz)
*2
Output of negative signals enabled when
Pr.290 Monitor negative output selection
= "1, 5, 9, or 13".
Current monitor reference (Pr.56)
• Enter the full scale value of a meter used to monitor the output current, the output current peak value, or the motor
excitation current via terminal FM or terminal AM.
• For the FM type inverter, enter the full-scale value of the meter corresponding to a pulse train of 1440 pulses/s output via
terminal FM. Enter the current value at full scale of the meter (1 mA analog meter) installed between terminal FM and
terminal SD. Pulse speed is proportional to the output current monitored. (The maximum pulse train output is 2400 pulses/
s.)
• Enter the full-scale value of the current meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the
current value at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 5. Output voltage is
proportional to the output current monitored. (The maximum output voltage is 10 VDC.)
Torque monitor reference (Pr.866)
• Enter the full-scale value of the meter used to monitor the output torque via terminal FM or terminal AM.
• For the FM type inverter, enter the full-scale value of the torque meter corresponding to a pulse train of 1440 pulses/s
output via terminal FM. Enter the torque value at full scale of the meter (1 mA analog meter) installed between terminal FM
and terminal SD. Pulse speed is proportional to the torque monitored. (The maximum pulse train output is 2400 pulses/s.)
• Enter the full-scale value of the torque meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the torque
value at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 5. Output voltage is
proportional to the torque monitored. (The maximum output voltage is 10 VDC.)
Terminal FM pulse train output
• The maximum pulse train output of terminal FM is 8 VDC 2400 pulses/s.
The pulse width can be adjusted on the operation panel by using the calibration parameter
C0 (Pr.900) FM terminal
calibration
.
• A 1 mA full-scale DC ammeter or a digital meter can be used to give commands (such as inverter output frequency
command).
1Hz
60Hz
(initial value)
Output frequency
590Hz
Setting range of
Pr.55
2400
1440
Pulse speed (pulses/s)
Setting range of
Pr.55
10VDC
60Hz
(initial value)
590Hz
-10VDC
60Hz
*2
Output voltage
*1
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...