127
5. Speed Control
5.7 Torque bias
1
2
3
4
5
6
7
8
9
10
• To input the X42 signal, set "42" in any of
Pr.178 to Pr.189 (Input terminal function selection)
to assign the function to
a terminal, and to input the X43 signal, set "43".
When
Pr.841
= "1025", the torque bias is 25%. When
Pr.842
= "975", the torque bias is -25%. When
Pr.843
= "925", the torque
bias is -75%.
NOTE
• Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function selection)
may affect the other functions.
Set parameters after confirming the function of each terminal.
Setting the torque bias amount using terminal 4 (Pr.840 ="1 or 2", Pr.847,
Pr.848)
• Calculate the torque bias from the load input to terminal 4 as shown in the following diagram, and then apply the torque
bias.
• To set the torque bias amount with a voltage input to terminal 4, set
Pr.858 Terminal 4 function assignment
= "6".
• The torque bias amount (
Pr.847
) and gain amount (
Pr.848
) when descending (reverse motor rotation when the
Pr.840
setting is "1", forward motor rotation when the setting is "2") can be set in a range of 0% to 400%. When
Pr.847 or
Pr.848
="9999", the setting is the same for both descending and ascending (
C38 to C41
).
*1
When the LX signal is ON, the torque bias amount when ascending is applied regardless of the motor rotation direction.
*2
In
Pr.846
, set the input voltage/current at a balanced load in %, considering the full-scale value of the voltage input via terminal 4 as 100%.
Torque bias selection 1
(X42)
Torque bias selection 2
(X43)
Torque bias amount
OFF
OFF
0%
ON
OFF
Pr.841
-400% to +400% (Setting value: 600% to
1400%)
OFF
ON
Pr.842
-400% to +400% (Setting value: 600% to
1400%)
ON
ON
Pr.843
-400% to +400% (Setting value: 600% to
1400%)
Pr.840
setting
When ascending
When descending
1
(Forward motor rotation)
(Reverse motor rotation)
2
(Reverse motor rotation)
(Forward motor rotation)
Pr.267 setting
Terminal 4 input
Input voltage/current for the balanced load (Pr.846 = "50")
0
4 to 20 mA
20 mA × 50% = 10 mA
1
0 to 5 V
5 V × 50% = 2.5 V
2
0 to 10 V
10 V × 50% = 5 V
Torque command
terminal 4 gain
C40(Pr. 933)
Torque command
terminal 4 bias
C38(Pr. 932)
Voltage for max. load
C41(Pr. 933)
Input voltage for
the balanced load
Pr. 846
Terminal 4
input
Bias amount
C39(Pr. 932)
Voltage for max. load
C41(Pr. 933)
Input voltage for
the balanced load
Pr. 846
Bias amount
Terminal 4
input
Fall-time
torque bias
terminal 4
bias
Pr. 847
Fall-time
torque bias
terminal 4
gain
Pr. 848
C39(Pr. 932)
Torque command
terminal 4 gain
C40(Pr. 933)
Voltage for max. load
C41(Pr. 933)
Input voltage for
the balanced load
Pr. 846
Bias amount
Terminal 4
input
Torque command
terminal 4 bias
C38(Pr. 932)
C39(Pr. 932)
Voltage for max. load
C41(Pr. 933)
Input voltage for
the balanced load
Pr. 846
Bias amount
Terminal 4
input
Fall-time
torque bias
terminal 4
bias
Pr. 847
Fall-time
torque bias
terminal 4
gain
Pr. 848
C39(Pr. 932)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...