12. (M) Item and Output Signal for Monitoring
12.10 Remote output function
12.10
Remote output function
The signal can be turned ON or OFF via the output terminal on the inverter as if the terminal is the remote output terminal for
a programmable controller.
Remote output setting (REM signal, Pr.496, Pr.497)
• The signal assigned to each of the output terminal can be turned ON or OFF according to the settings of
Pr.496
and
Pr.497
.
The signal assigned to each of the remote output terminal can be turned ON or OFF through communication.
• To use the Remote output (REM) signal, set "96" (positive logic) or "196" (negative logic) in any parameter from
Pr.190 to
Pr.192 (Output terminal function selection)
to assign the function to the terminal.
• Refer to the following figures to check correspondences between the bit and the actual terminal. When "1" is set in the bit
corresponding to the terminal to which the REM signal assigned by setting a number in
Pr.496
and
Pr.497
each, the signal
turns ON (or OFF in negative logic setting). Also, setting "0" allows the signal to turn OFF (or ON in negative logic setting).
• For example, when
Pr.190 RUN terminal function selection
= "96" (positive logic) and "1" (H01) is set in
Pr.496
, the REM
signal assigned to terminal RUN turns ON.
Pr.496
Pr.497
*1
Any value
*2
Y0 to Y6 are available by installing the output-extending option (FR-A8AY) or via communication.
*3
RA1 to RA3 are available by installing the relay output option (FR-A8AR) or via communication.
Remote output data retention (REM signal, Pr.495)
• When the inverter power is reset (or a power failure occurs) while
Pr.495
= "0 (initial value) or 10", the REM signal setting
is cleared. (The ON/OFF state of the signal assigned to each terminal is determined by the settings in
Pr.190 to Pr.192
.)
The settings in
Pr.496
and
Pr.497
are reset to "0".
• When
Pr.495
= "1 or 11", the remote output data is stored in EEPROM before the inverter power is turned OFF. This means
that the signal output setting after power restoration is the same as that before the power was turned OFF. However, when
Pr.495
= "1", the data during an inverter reset (terminal reset or reset request via communication) is not saved.
Pr.
Name
Initial value
Setting
range
Description
495
M500
Remote output selection
0
0
Remote output data is cleared when
the inverter power is turned OFF.
Remote output data is cleared
during an inverter reset.
1
Remote output data is retained even
after the inverter power is turned OFF.
10
Remote output data is cleared when
the inverter power is turned OFF.
Remote output data is retained
during an inverter reset.
11
Remote output data is retained even
after the inverter power is turned OFF.
496
M501
Remote output data 1
0
0 to 4095
Set a decimal number to enter a binary number in every bit
corresponding to each of the output terminals of the inverter or
communication.
497
M502
Remote output data 2
0
0 to 4095
Set a decimal number to enter a binary number in every bit
corresponding to each of the output terminals of the option FR-A8AY or
FR-A8AR, or communication.
b11
b0
ABC
*1
*1
*1
*1
*1
*1
*1
*1
*1
FU
RUN
b11
b0
Y5
∗2
Y6
∗2
RA1
∗3
RA2
∗3
RA3
∗3
∗1
∗1
Y4
∗2
Y3
∗2
Y2
∗2
Y1
∗2
Y0
∗2
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...