384
15. (A) Application Parameters
15.4 PID control
• Switch the power voltage/current specifications of terminals 2 and 4 by
Pr.73 Analog input selection
or
Pr.267 Terminal
4 input selection
to match the specification of the input device. After changing the
Pr.73 or Pr.267
settings, check the
voltage/current input selection switch. Incorrect setting may cause a fault, failure, or malfunction. (Refer to
for
the setting.)
*1
When
Pr.133
≠
"9999", the
Pr.133
setting is valid.
*2
CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For the details of each communication, refer to the FR-
A8NC E kit Instruction Manual or the Instruction Manual (Communication).
• The set point/deviation input method can also be flexibly selected by
Pr.609 PID set point/deviation input selection
and
the measured value input method can be selected by
Pr.610 PID measured value input selection
. Selection by
Pr.609
and Pr.610
is valid when
Pr.128
= "1000 to 2011".
*3
When the same input method has been selected for the set point and measured value at
Pr.609
and
Pr.610
, set point input is invalid. (Inverter
runs at set point 0%)
*4
CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For details on communication, refer to the Instruction
Manual of each option.
NOTE
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using
C3 (Pr.902)
and
C6 (Pr.904)
to prevent
a minus voltage from being entered as the deviation input signal. Input of a minus voltage might damage devices and the
inverter.
Pr.128
setting
Pr.609
Pr.610
PID action
Set point input
Measured value input
Deviation input
0
Invalid
PID invalid
—
—
—
20
Reverse action
Terminal 2 or
Pr.133
Terminal 4
—
21
Forward action
40 to 43
Enabled
Dancer control
For details on dancer control, refer to
50
Invalid
Reverse action
—
—
Communication
51
Forward action
60
Reverse action
Communication
Communication
—
61
Forward action
1000
Enabled
Reverse action
According to
Pr.609
According to
Pr.610
—
1001
Forward action
1010
Reverse action
—
—
According to
Pr.609
1011
Forward action
2000
Reverse action (without
frequency reflected)
According to
Pr.609
According to
Pr.610
—
2001
Forward action (without
frequency reflected)
2010
Reverse action (without
frequency reflected)
—
—
According to
Pr.609
2011
Forward action (without
frequency reflected)
Pr.609 to Pr.610 settings
Input method
2
Terminal 2
3
Terminal 4
4
5
PLC function
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...