11
12
13
14
15
16
17
18
19
20
431
16. (G) Control Parameters
16.3 Load pattern selection
•
Pr.46 Second torque boost
is enabled when the RT signal is ON. To input the RT signal, set "3" in any parameter from
Pr.178 to Pr.189 (Input terminal function selection)
to assign the function.
NOTE
• When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in
Pr.19 Base frequency
voltage
to prevent trip due to current at regeneration.
Parameters referred to
Pr.0 Torque boost
Pr.178 to Pr.189 (Input terminal function selection)
Pr.14
= 2
Pr.14
= 3
100%
Forward
rotation
Pr.0
Output
voltage
Base frequency
Output frequency (Hz)
For vertical lift loads
At forward rotation boost...
Pr.0
setting
At reverse rotation boost...0%
Reverse
rotation
100%
Reverse
rotation
Pr.0
Output
voltage
Base frequency
Output frequency (Hz)
For vertical lift loads
At forward rotation boost...0%
At reverse rotation boost...
Pr.0
setting
Forward
rotation
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...