12. (M) Item and Output Signal for Monitoring
12.6 Output terminal function selection
12
112
Y12
Output current detection
Output when the output current is higher
than the
Pr.150
setting for the time set in
Pr.151
or longer.
Pr.150, Pr.151
13
113
Y13
Zero current detection
Output when the output current is lower than
the
Pr.152
setting for the time set in
Pr.153
or longer.
Pr.152, Pr.153
14
114
FDN
PID lower limit
Output when the input value is lower than
the lower limit set for the PID control
operation.
Pr.127 to
Pr.134, Pr.575
to Pr.577
15
115
FUP
PID upper limit
Output when the input value is higher than
the upper limit set for the PID control
operation.
16
116
RL
PID forward/reverse
rotation output
Output during forward rotation operation in
the PID control operation.
20
120
BOF
Brake opening request
Output to release the brake while the brake
sequence function is enabled.
Pr.278 to
Pr.285, Pr.292
25
125
FAN
Fan fault output
Output when a fan fault occurs.
Pr.244
26
126
FIN
Heat sink overheat pre-
alarm
Output when the heat sink temperature rises
to 85% of temperature at which the
protective function of the Heat sink overheat
is activated.
—
Instruction
Manual
(Maintenance)
30
130
Y30
Forward rotation output
(output for a Vector
control compatible
option)
Output while a motor rotates in forward
direction.
—
31
131
Y31
Reverse rotation output
(output for a Vector
control compatible
option)
Output while a motor rotates in reverse
direction.
32
132
Y32
Regenerative status
output (output for a Vector
control compatible
option)
Output while a motor is in a regenerative
braking state under Vector control.
33
133
RY2
Operation ready 2
Output while pre-excitation is enabled or
during normal operation under Real
sensorless vector control, Vector control, or
PM sensorless vector control.
—
34
134
LS
Low speed detection
Output when the output frequency drops to
the
Pr.865
setting or lower.
Pr.865
35
135
TU
Torque detection
Output when the motor torque is higher than
the
Pr.864
setting.
Pr.864
39
139
Y39
Start time tuning
completion
Output when the start-time tuning complete.
Pr.95, Pr.574
40
140
Y40
Trace status
Output during trace operation.
Pr.1020,
Pr.1022 to
Pr.1047
41
141
FB
Speed detection
Output when the actual motor rotations per
minute (estimate) reaches the setting of
Pr.42
.
Pr.42
44
144
RUN2
Inverter running 2
Output while the Forward rotation command
signal or Reverse rotation command signal
is ON. Output during deceleration even
while the Forward rotation command signal
or Reverse rotation command signal is OFF
—
45
145
RUN3
Inverter running and start
command ON
Output while the inverter is running or while
the start command signal is ON.
—
46
146
Y46
During deceleration at
occurrence of power
failure
Output when the power-failure deceleration
function is activated.
(The signal output is retained until the
function stops.)
Pr.261
47
147
PID
During PID control
activated
Output during the PID control operation.
Pr.127 to
Pr.134, Pr.575
to Pr.577
Setting
Signal
name
Function
Operation
Related
parameter
Refer to page
Positive
logic
Negative
logic
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...