15. (A) Application Parameters
15.12 Trace function
15.12
Trace function
• The operating status of the inverter can be traced and temporarily stored in the RAM in the inverter. The data stored in the
RAM is deleted when the power supply is turned OFF. (The data is retained at inverter reset.)
• Stored data can be monitored by FR Configurator2, and the status of the inverter can be analyzed.
Pr.
Name
Initial value
Setting range
Description
1020
A900
Trace operation selection
0
0
Without trace operation
1
Sampling start
2
Forced trigger
3
Sampling stop
1022
A902
Sampling cycle
1
1, 2, 5, 10, 50,
100, 500, 1000
Set the sampling cycle.
1: 1 ms, 2: 2 ms, 5: 5 ms, 10: 10 ms, 50: 50 ms, 100: 100 ms,
500: 500 ms, 1000: 1 s
1023
A903
Number of analog channels
4
1 to 8
Select the number of analog channels for sampling.
1024
A904
Sampling auto start
0
0
Manual sampling start
1
Sampling starts automatically when the power supply is turned
ON or at a reset
1025
A905
Trigger mode selection
0
0
Fault trigger
1
Analog trigger
2
Digital trigger
3
Analog or digital trigger (OR logic)
4
Both analog and digital triggers (AND logic)
1026
A906
Number of sampling before
trigger
90%
0% to 100%
Set the percentage of the pre-trigger sampling time with
respect to the overall sampling time.
1027
A910
Analog source selection (1ch)
201
1 to 3, 5 to 14, 17
to 20, 23, 24, 32,
33, 35, 40 to 42,
52 to 54, 61, 62,
67, 83, 91, 97,
201 to 210, 212,
213, 230 to 232,
235 to 238
Select the analog data (monitor item) for sampling on each
channel.
1028
A911
Analog source selection (2ch)
202
1029
A912
Analog source selection (3ch)
203
1030
A913
Analog source selection (4ch)
204
1031
A914
Analog source selection (5ch)
205
1032
A915
Analog source selection (6ch)
206
1033
A916
Analog source selection (7ch)
207
1034
A917
Analog source selection (8ch)
208
1035
A918
Analog trigger channel
1
1 to 8
Select the analog channel to be the trigger.
1036
A919
Analog trigger operation
selection
0
0
Sampling starts when the value of the analog monitor exceeds
the value set at the trigger level (
Pr.1037
)
1
Sampling starts when the value of the analog monitor falls
below the value set at the trigger level (
Pr.1037
)
1037
A920
Analog trigger level
1000
600 to 1400
Set the level at which the analog trigger turns ON.
The trigger level is the value obtained by subtracting 1000 from
the set value.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...