6. Torque Control
6.4 Torque command
• Torque commands given by analog inputs can be calibrated by the calibration parameters
C38 (Pr.932) to C41 (Pr.933)
Torque command given by parameter (Pr.804 = "1")
• Set
Pr.805 Torque command value (RAM)
or
Pr.806 Torque command value (RAM, EEPROM)
to set the torque
command value.
For
Pr.805
or
Pr.806
, regard 1000% as 0%, and set torque command by offset from 1000%.
The following diagram shows relation between the
Pr.805
or
Pr.806
setting and the actual torque command value.
• To change the torque command value frequently, write it in
Pr.805
. Writing values in
Pr.806
frequently will shorten the life
of the EEPROM.
NOTE
• When the torque command is set by
Pr.805
(RAM), powering OFF the inverter erases the changed parameter value.
Therefore, the parameter set value is the one saved by
Pr.806
(EEPROM) when the power is turned back on.
• If giving torque command by parameter setting, set the speed limit value properly to prevent overspeeding. (Refer to
Torque command via communication (Pr.804 = "3, 5, or 6")
• Set the torque command value via CC-Link (FR-A8NC / PLC function), CC-Link IE TSN, CC-Link IE Field Network Basic,
and PROFIBUS-DP (FR-A8NP) communication.
• For speed limit when "3 or 5" is set in
Pr.804
,
Pr.807 Speed limit selection
becomes invalid and
Pr.808 Speed limit
and
Pr.809 Reverse-side speed limit
become valid for speed limit. (When
Pr.544 CC-Link extended setting
= "0, 1, 12, 100,
or 112")
•
Pr.807
is valid when the extended cyclic setting of CC-Link communication is quadruple or octuple.
*1
They can also be set using the operation panel or parameter unit.
*2
When the FR-A8NP is installed, the torque command can be set only by
Pr.805
or
Pr.806
.
*3
On the operation panel or parameter unit, the setting range is "673 to 1327 (-327% to 327%)" and the setting increment is 1%.
Pr.804
setting
Torque command input
Setting range
Setting
increments
Required condition
1
Torque command by
Pr.805 or Pr.806
600 to 1400
(-400% to 400%)
1%
—
3
• Torque command by remote register
(RWw1 or RWwC)
• Torque command by
Pr.805 or Pr.806
FR-A8NC is installed, CC-Link
IE TSN or CC-Link IE Field
Network Basic is used, or FR-
A8NP is installed.
5
• Torque command by remote register
(RWw1 or RWwC)
• Torque command by
Pr.805 or Pr.806
-32768 to 32767 (complement of 2)
(-327.68% to 327.67%)
0.01%
6
Torque command by
Pr.805 or Pr.806
Torque command
150%
0
100%
Terminal 4
analog input
Torque command value
400%
600%
1000%
1400%
-400%
Pr.805, Pr.806
settings
Torque command value
=
Pr.805(or Pr.806)
-1000%
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...