417
15. (A) Application Parameters
15.11 PLC function
• When
Pr.414
= "2 or 12", the SQ signal can be input only via an external input terminal regardless of the
Pr.338
setting.
• The following shows the required conditions to enable the SQ signal.
—: Not required to enable the SQ signal
User parameter (data register (D)) auto storage function selection
• Setting
Pr.675
= "1" enables the auto storage function for user parameters.
• The user parameter auto storage function is used to store the setting of
Pr.1195 PLC function user parameters 46
(D251)
to
Pr.1199 PLC function user parameters 50
(D255) automatically in EEPROM at power OFF or inverter reset.
• The auto storage function is disabled while the inverter performs any of the following.
Measurement of the main circuit capacitor's life, offline auto tuning, or measurement of load characteristics
NOTE
• The auto storage function may fail if the EEPROM is accessed by other functions at the same time at power OFF. To ensure
the auto storage, provide a power source for the control circuit separately from that of the main circuit.
User parameter reading from EEPROM
• User parameters (
Pr.1150 to Pr.1199
) are read from RAM or EEPROM according to the settings in
Pr.342
Communication EEPROM write selection
and
Pr.414 PLC function operation selection
. When
Pr.414
= "11 or 12",
RAM data is read regardless of the
Pr.342
setting.
NOTE
• For the details of the PLC function, refer to the PLC Function Programming Manual and the Instruction Manual of FR
Configurator2.
Pr.414 setting
Pr.338 setting
SQ signal
Input via an external (physical) terminal
Input via a communication virtual terminal
1, 11
0
ON
ON
—
ON (terminal NET X)
1
ON
—
2, 12
—
ON
—
Device
Pr.342
Pr.414
Read from
Written to
Inverter (via communication),
FR Configurator2
0
0, 1, 2
EEPROM
EEPROM
11, 12
RAM
1
0, 1, 2
RAM
RAM
11, 12
RAM
Communication option
0
0, 1, 2
(Differs according to the option type.)
EEPROM
11, 12
RAM
1
0, 1, 2
RAM
RAM
11, 12
RAM
Operation panel
0
0, 1, 2
EEPROM
EEPROM
11, 12
RAM
1
0, 1, 2
EEPROM
RAM
11, 12
RAM
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...