58
3. Parameters
3.2 Parameter list (by parameter number)
PID op
eratio
n
127
A612
PID control automatic
switchover frequency
0 to 590 Hz, 9999
0.01 Hz
9999
128
A610
PID action selection
0, 20, 21, 40 to 43, 50,
51, 60, 61, 1000, 1001,
1010, 1011, 2000,
2001, 2010, 2011
1
0
,
129
A613
PID proportional band
0.1% to 1000%, 9999
0.1%
100%
,
130
A614
PID integral time
0.1 to 3600 s, 9999
0.1 s
1 s
,
131
A601
PID upper limit
0% to 100%, 9999
0.1%
9999
,
132
A602
PID lower limit
0% to 100%, 9999
0.1%
9999
,
133
A611
PID action set point
0% to 100%, 9999
0.01%
9999
,
134
A615
PID differential time
0.01 to 10 s, 9999
0.01 s
9999
,
PU
145
E103
PU display language
selection
0 to 7
1
—
—
147
F022
Acceleration/deceleration
time switching frequency
0 to 590 Hz, 9999
0.01 Hz
9999
Current
det
ectio
n
150
M460
Output current detection
level
0% to 400%
0.1%
150%
151
M461
Output current detection
signal delay time
0 to 10 s
0.1 s
0 s
152
M462
Zero current detection level
0% to 400%
0.1%
5%
153
M463
Zero current detection time
0 to 10 s
0.01 s
0.5 s
—
154
H631
Voltage reduction selection
during stall prevention
operation
1, 11
1
1
—
156
H501
Stall prevention operation
selection
0 to 31, 100, 101
1
0
—
157
M430
OL signal output timer
0 to 25 s, 9999
0.1 s
0 s
,
—
158
M301
AM terminal function
selection
[E800-4][E800-5]
1 to 3, 5 to 14, 17, 18,
21, 24, 32, 33, 50, 52
to 54, 61, 62, 67, 70,
91, 97
1
1
—
160
E440
User group read
selection
0, 1, 9999
1
0
—
161
E200
Frequency setting/key lock
operation selection
0, 1, 10, 11
1
0
Au
tom
atic
res
tart
162
A700
Automatic restart after
instantaneous power failure
selection
0, 1, 10, 11
1
0
,
,
165
A710
Stall prevention operation
level for restart
0% to 400%
0.1%
150%
Current
det
ectio
n
166
M433
Output current detection
signal retention time
0 to 10 s, 9999
0.1 s
0.1 s
167
M464
Output current detection
operation selection
0, 1, 10, 11
1
0
—
168
E000
Parameter for manufacturer setting. Do not set.
E080
—
169
E001
E081
Function
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial
value
*1
Refer
to page
Customer
setting
Gr.1
Gr.2
Simple
Simple
Simple
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...