114
5. Speed Control
5.4 Setting the torque limit level
5.4
Setting the torque limit level
Limit the output torque not to exceed the specified value.
The torque limit level can be set in a range of 0% to 400%. The TL signal can be used to switch between two types of torque
limit.
The torque limit level can be selected by setting it with a parameter, or by using the analog input terminal (terminal 4). Also, the
torque limit levels of forward rotation (power driving/regenerative driving) and reverse rotation (power driving/regenerative
driving) can be set individually.
Pr.
Name
Initial value
Setting
range
Description
22
H500
Stall prevention operation
level (Torque limit level)
150% / 200%
0% to 400%
Set the torque limit level as a percentage with regards to the rated
torque as 100%.
157
M430
OL signal output timer
0 s
0 to 25 s
Set the OL signal output start time at the activation of torque limit
operation.
9999
No OL signal output.
801
H704
Output limit level
9999
0% to 400%
Set the torque current limit level.
9999
The torque limit setting value is used for limiting the torque current
level.
803
G210
Constant output range
torque characteristic
selection
0
0
The torque rises in the low-
speed range.
The motor power output is
limited to be constant in the
constant power range.
1
The torque is kept constant in
the low-speed range.
The torque is limited to be
constant in the constant power
range.
2
The torque is kept constant in
the low-speed range. (The
torque current is limited.)
The torque is limited to be
constant in the constant power
range unless the output limit of
the torque current is reached.
(The torque current is limited.)
10
The torque is kept constant in
the low-speed range.
The motor power output is
limited to be constant in the
constant power range.
804
D400
Torque command source
selection
0
0
Torque command given by analog input via terminal 4
1
Torque limit by the parameter setting (
Pr.805
or
Pr.806
)
(-400% to 400%)
3
Torque limit via communication
4
The internal torque limit 2 cannot be used
5
Torque limit via communication
6
805
D401
Torque command value
(RAM)
1000%
600% to
1400%
Writes the torque limit value in RAM. Regards 1000% as 0%, and
set torque command by an offset of 1000%.
806
D402
Torque command value
(RAM, EEPROM)
1000%
600% to
1400%
Writes the torque limit value in RAM and EEPROM.
Regards 1000% as 0%, and set torque command by an offset of
1000%.
810
H700
Torque limit input method
selection
0
0
Internal torque limit 1 (torque limited by parameter settings)
1
External torque limit (torque limited by terminal 4)
2
Internal torque limit 2 (torque limited via communication)
811
D030
Set resolution switchover
0
0
Torque limit setting increments 0.1%
10
Torque limit setting increments 0.01%
812
H701
Torque limit level
(regeneration)
9999
0% to 400%
Set the torque limit level for forward rotation regenerative driving.
9999
Limit using
Pr.22
or the analog terminal values.
813
H702
Torque limit level (3rd
quadrant)
9999
0% to 400%
Set the torque limit level for reverse rotation power driving.
9999
Limit using
Pr.22
or the analog terminal values.
814
H703
Torque limit level (4th
quadrant)
9999
0% to 400%
Set the torque limit level for reverse rotation regenerative driving.
9999
Limit using
Pr.22
or the analog terminal values.
815
H710
Torque limit level 2
9999
0% to 400%
When the torque limit selection (TL) signal is ON,
Pr.815
is the
torque limit value regardless of
Pr.810
.
9999
The torque limit set to
Pr.810
is valid.
Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...