16. (G) Control Parameters
16.6 DC injection brake, zero speed control, servo lock, and magnetic flux decay output shutoff
16.6
DC injection brake, zero speed control, servo lock,
and magnetic flux decay output shutoff
• Adjust the braking torque and timing to stop the motor using the DC injection brake.
Zero speed control is also available under Real sensorless vector control, and zero speed control and servo lock are
selectable under Vector control.
When the DC injection brake operation is used, DC voltage is applied to the motor to prevent rotation of the motor shaft,
and when the zero speed control is used, Vector control is performed to keep 0 r/min. Either way, when a motor shaft is
rotated by external force, it does not go back to the original position.
When the servo lock control is used, the position of the motor shaft is held. When a motor shaft is rotated by external force,
it goes back to the original position.
• Select the magnetic flux decay output shutoff function to decay the magnetic flux before shutting off the output at a stop.
*1
The initial value differs depending on the inverter capacity.
Setting of operating frequency (Pr.10)
• By setting the frequency for DC injection brake operation (zero speed control / servo lock) to
Pr.10 DC injection brake
operation frequency
, DC injection brake operation (zero speed control / servo lock) starts when the frequency reaches
the
Pr.10
setting during deceleration.
Pr.
Name
Initial value
Setting range
Description
10
G100
DC injection brake
operation frequency
3 Hz
0 to 120 Hz
Set the operation frequency for the DC injection brake (zero speed
control / servo lock).
11
G101
DC injection brake
operation time
0.5 s
0
DC injection brake operation (zero speed control / servo lock) is not
applied.
0.1 to 10 s
Set the operation time for the DC injection brake (zero speed
control / servo lock).
8888
The operation continues while the X13 signal is ON.
12
G110
DC injection brake
operation voltage
6% / 4% /
1%
0% to 30%
Set the DC injection brake voltage (torque). When set to "0", the DC
injection brake is not applied.
802
G102
Pre-excitation
selection
0
0
Zero speed control
1
Servo lock
850
G103
Brake operation
selection
0
0
DC injection brake operation is applied.
1
Zero speed control (under Real sensorless vector control)
2
Magnetic flux decay output shutoff (under Real sensorless vector
control)
422
B003
Position control gain
10 s
-1
0 to 150 s
-1
Set the position control gain for servo lock.
Inverter
Initial value
FR-E820-0015(0.2K) or lower
FR-E820S-0015(0.2K) or lower
6%
FR-E820-0030(0.4K) or higher
FR-E840-0016(0.4K) or higher
FR-E820S-0030(0.4K) or higher
4%
FR-E860-0017(0.75K) or higher
1%
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...