15. (A) Application Parameters
15.8 Automatic restart after instantaneous power failure / flying start with a PM motor
15.8
Automatic restart after instantaneous power failure
/ flying start with a PM motor
The inverter can be restarted without stopping the motor operation.
When the automatic restart after instantaneous power failure function is selected, the motor driving is resumed in the following
situations:
• When power comes back ON during inverter driving after an instantaneous power failure
• When the motor is coasting at start
Selection of restart operation (Pr.162)
• At a power restoration, the encoder detects the motor speed by a frequency search so that the inverter can re-start
smoothly.
• The encoder also detects the rotation direction so that the inverter can re-start smoothly even during the reverse rotation.
• When "10 (or 11)" is set in
Pr.162
, a restart operation is performed at each start and automatic restart after instantaneous
power failure. When "0 (or 1)" is set in
Pr.162
, a restart operation is performed at the first start after a power-ON, and from
the second power-ON onwards, a start from the starting frequency is performed.
NOTE
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• Restart operation with reduced voltage is not available for PM sensorless vector control.
• A protective function may be activated for some motor models or at certain running speeds, disabling restarting.
Restart coasting time (Pr.57)
• Coasting time is the time from the motor speed detection to the restart operation start.
• To enable restart operation, set "0" (no coasting time) in
Pr.57 Restart coasting time
. Generally, this setting does not
interfere with inverter operation.
PM
PM
PM
Pr.
Name
Initial value
Setting range
Description
57
A702
Restart coasting time
9999
0
No delay
0.1 to 30 s
Set the delay time for the inverter to perform a restart after restoring
power due to an instantaneous power failure.
9999
No restart
162
A700
Automatic restart after
instantaneous power
failure selection
0
0, 1
Frequency search only performed at the first start
10, 11
Frequency search at every start
611
F003
Acceleration time at a
restart
9999
0 to 3600 s
Set the acceleration time to reach
Pr.20 Acceleration/deceleration
reference frequency
at restart.
9999
Standard acceleration time (for example,
Pr.7
) is applied as the
acceleration time at restart.
Instantaneous (power failure) time
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (V)
Coasting
time (
Pr.57
)
Speed
detection
time
+
Acceleration time
at a restart
(
Pr.611
setting)
*
The output shut off timing differs
according to the load condition
*
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...