15. (A) Application Parameters
15.4 PID control
• When
Pr.127 PID control automatic switchover frequency
is set, the startup is made without PID control until the output
frequency reaches the
Pr.127
setting. Once the PID control starts, the PID control is continued even if the output frequency
drops to
Pr.127
setting or lower.
Operation selection and sleep function stop selection when a value error
is detected (FUP signal, FDN signal, Y48 signal, Pr.554)
• Using
Pr.554 PID signal operation selection
, set the action when the measured value input exceeds the upper limit
(
Pr.131 PID upper limit
) or lower limit (
Pr.132 PID lower limit
), or when the deviation input exceeds the permissible value
(
Pr.553 PID deviation limit
).
• Choose whether to output the signals (FUP, FDN, Y48) only or to activate the protective function to output the inverter
shutoff.
• The stop action when the inverter output is shut off by the sleep function can be selected.
*1
When each of
Pr.131, Pr.132
and
Pr.553
settings corresponding to each of the FUP, FDN and Y48 signals is "9999" (no function), signal output
and protective function are not available.
PID output suspension function (sleep function) (SLEEP signal, Pr.575 to
Pr.577)
• When a status where the output frequency after PID calculation is less than
Pr.576 Output interruption detection level
has continued for the time set in
Pr.575 Output interruption detection time
or longer, inverter running is suspended. This
allows the amount of energy consumed in the inefficient low-speed range to be reduced.
• When the deviation (set point - measured value) reaches the PID output shutoff release level (
Pr.577
setting value -1000%)
while the PID output suspension function is activated, the PID output suspension function is released, and PID control
operation is automatically restarted.
• Whether to allow motor to coast to a stop or perform a deceleration stop when sleep operation is started can be selected
using
Pr.554
.
• While the PID output suspension function is activated, the PID output interruption (SLEEP) signal is output. During this
time, the Inverter running (RUN) signal turns OFF and the During PID control activated (PID) signal turns ON.
Pr.554 setting
Inverter operation
At FUP/FDN signal output
At Y48 signal output
At sleep operation start
0 (initial value)
Signal output only
Signal output only
Coasts to stop
1
Signal output shutoff (E.PID)
2
Signal output only
Signal output shutoff (E.PID)
3
Signal output shutoff (E.PID)
10
Signal output only
Signal output only
Deceleration stop
11
Signal output shutoff (E.PID)
12
Signal output only
Signal output shutoff (E.PID)
13
Signal output shutoff (E.PID)
Output frequency
Pr.127
STF
Time
PID
PID control
Without PID
control
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...