145
6. Torque Control
6.4 Torque command
1
2
3
4
5
6
7
8
9
10
NOTE
• For the details of the CC-Link communication, refer to the FR-A8NC E kit Instruction Manual. For the details of the CC-Link IE
TSN or CC-Link IE Field Network, refer to the Instruction Manual (Communication). For the details of the PROFIBUS-DP
communication, refer to the FR-A8NP E kit Instruction Manual.
• For details of the setting using the PLC function, refer to the PLC Function Programming Manual.
• CC-Link and PROFIBUS-DP communication are unavailable when the Vector control compatible options is installed.
Torque command given by 16-bit digital input (Pr.804 = "4")
• Give the torque command by 12-bit or 16-bit digital input using FR-A8AX (plug-in option) under Real sensorless vector
control.
NOTE
• For details of the setting using the FR-A8AX, refer to the FR-A8AX E kit Instruction Manual.
Changing the torque characteristic of the constant-power range (Pr.801,
Pr.803)
• According to the motor's characteristics, the torque decreases at the frequency equal to or higher than the base frequency.
To give the constant torque command at the speed equal to or higher than the base frequency, set "1" in
Pr.803 Constant
output range torque characteristic selection
.
• Torque in a low-speed range is constant during torque control regardless of the setting of
Pr.803
. However, when "2" is
set in
Pr.803
under Real sensorless vector control, the torque may not be kept constant in the low-speed range due to a
condition such as the
Pr.801
setting.
• To avoid overload or overcurrent of the inverter or motor, use
Pr.801 Output limit level
to limit the torque current in the
constant power range.
Pr.803 setting
Torque characteristic in constant-power range
Torque characteristic
Output limit
0 (initial value), 10
Constant motor output
—
1
Constant torque
Unlimited
2
Constant torque
Limited
Pr.801 setting
Description
0% to 400%
Set the torque current limit level.
9999
The torque limit setting value (
Pr.22, Pr.812 to Pr.817
, etc.) is used for limiting the torque current.
Speed
Rated speed
Torque
Pr.803
=1:
constant torque command
Pr.803
=0, 10:
constant power command
Constant torque range
Constant power range
Pr.803
=0, 1, 10
Speed
Rated speed
Pr.801
Torque
Pr.803
= 2
Constant torque
command
When the output limit
is not exceeded
Torque reduction
when the output is
limited
Constant torque range
Constant power range
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...