11
12
13
14
15
16
17
18
19
20
311
13. (T) Multi-Function Input Terminal Parameters
13.1 Analog input selection
Analog input specification selection
• For terminals 2 and 4 used for analog input, the voltage input (0 to 5 V, 0 to 10 V) and current input (0 to 20 mA) are
selectable. To change the input specification, change the setting of
Pr.73 (Pr.267)
and the voltage/current input selection
switch (switch 2 or switch 4).
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Set
Pr.73 (Pr.267)
and the voltage/current input selection switch according to the analog signal input. The incorrect
settings shown in the following table cause a failure. The inverter does not operate properly with other incorrect settings.
Set
Pr.73
and the voltage/current input selection switch according to the following table.
• When the Terminal 4 input selection (AU) signal is turned ON, terminal 4 is used to set the main speed. In this case,
terminal 2 is not used to set the main speed.
Switch state
Input specification
Input
terminal
Rated specification
Switch 2
I
Current input
Terminal 2
For voltage input, the input resistance is 10±1 k
Ω
and the
maximum permissible voltage is 20 VDC.
For current input, the input resistance is 245±5
Ω
and the
maximum permissible current is 30 mA.
V
Voltage input (initial status)
Switch 4
I
Current input (initial status)
Terminal 4
V
Voltage input
Voltage/current
input switch
Voltage/current
input switch
Switch 2
Switch 4
Switch 2
Switch 4
I
V
2
4
2
4
Voltage/current
input switch
Switch 2
Switch 4
I
V
2
4
Standard model
Ethernet model
,
9
Safety communication model
Setting causing a failure
Operation
Switch setting
Terminal input
I (current input)
Voltage input
Causes an analog signal output circuit failure in an external device (due to increased loads on the
signal output circuit of the external device).
V (voltage input)
Current input
Causes an input circuit failure in the inverter (due to an increased output power in the analog signal
output circuit of an external device).
Pr.73 setting
Terminal 2 input
Switch 2
Reversible operation
0
0 to 10 V
V
Disabled
1 (initial value)
0 to 5 V
V
6
0 to 20 mA
I
10
0 to 10 V
V
Enabled
11
0 to 5 V
V
16
0 to 20 mA
I
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...