10. (D) Operation Command and Frequency Command
10.1 Operation mode selection
Operation mode selection flow
Referring to the following table, select the basic parameter settings or terminal wiring related to the operation mode.
External operation mode (Pr.79 = "0 (initial value) or 2")
• Select the External operation mode when the start command and the frequency command are applied from a frequency
setting potentiometer, start switch, etc. which are provided externally and connected to the control circuit terminals of the
inverter.
• Generally, parameter change cannot be performed in the External operation mode. (Some parameters can be changed.
Refer to
,)
• When
Pr.79
= "0 or 2", the inverter starts up in the External operation mode at power-ON. (When using the Network
operation mode, refer to
.)
Method to give
start command
Method to give
frequency setting
command
Parameter setting
Operation method
Start command
Frequency setting
External signals
(via terminal STF/
STR)
External signals (input via
terminal 2 or 4, using the
JOG signal, using the
multi-speed setting
function, etc.)
Pr.79
= "2"
(Fixed at External operation
mode)
Turn ON terminal
STF/STR.
Turn ON a terminal used for
frequency setting.
Operation panel
Pr.79
= "3"
(External/PU combined
operation mode 1)
Turn ON terminal
STF/STR.
Digital setting
USB connector
Pr.79
= "3"
(External/PU combined
operation mode 1)
Turn ON terminal
STF/STR.
Digital setting
Communication (PU
connector / Ethernet
connector)
Pr.338
= "1"
Pr.340
= "1"
Turn ON terminal
STF/STR.
Transmit a frequency command via
communication.
Communication (via
communication option)
Pr.338
= "1"
Pr.340
= "1"
Turn ON terminal
STF/STR.
Transmit a frequency command via
communication.
Operation panel
(RUN key)
External signals (input via
terminal 2 or 4, using the
JOG signal, using the
multi-speed setting
function, etc.)
Pr.79
= "4"
(External/PU combined
operation mode 2)
Press the RUN key.
Turn ON a terminal used for
frequency setting.
Operation panel
Pr.79
= "1"
(Fixed at PU operation mode)
Press the RUN key. Digital setting
• USB connector
• Communication (PU
connector / Ethernet
connector /
communication option)
Not available
Communication
(PU connector /
Ethernet connector)
External signals (input via
terminal 2 or 4, using the
JOG signal, using the
multi-speed setting
function, etc.)
Pr.339
= "1"
Pr.340
= "1"
Transmit a start
command via
communication
Turn ON a terminal used for
frequency setting.
• USB connector
• Communication (via
communication option)
Not available
Communication (PU
connector / Ethernet
connector)
Pr.340
= "1"
Transmit a start
command via
communication
Transmit a frequency command via
communication.
Communication
(via communication
option)
External signals (input via
terminal 2 or 4, using the
JOG signal, using the
multi-speed setting
function, etc.)
Pr.339
= "1"
Pr.340
= "1"
Transmit a start
command via
communication
Turn ON a terminal used for
frequency setting.
• USB connector
• Communication (PU
connector / Ethernet
connector)
Not available
Through communication
(via communication
option)
Pr.340
= "1"
Transmit a start
command via
communication
Transmit a frequency command via
communication.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...