14. (C) Motor Constant Parameters
14.5 Parameter settings for a motor with encoder
Parameter settings for the motor under Vector control
*1
Offline auto tuning is required. (Refer to
*2
Set this parameter according to the motor.
*3
Use the thermal protector input provided with the motor.
*4
When using a motor equipped with a thermal protector, set "0" to protect the motor from overheating.
• When using the inverter with the SF-V5RU (1500 r/min series), refer to the following table to set
Pr.83 Rated motor
voltage
and
Pr.84 Rated motor frequency
.
Combination with the Vector control dedicated motor
When using the inverter with a Vector control dedicated motor, refer to the following table.
Motor model
Pr.9
Electronic
thermal O/L
relay
Pr.71
Applied
motor
Pr.80
Motor capacity
Pr.81
Number of
motor poles
Pr.359
Encoder
rotation
direction
Pr.369
Number of
encoder
pulses
Mitsubishi
Electric high-
performance
energy-saving
motor with
encoder
SF-PR-SC
Rated motor
current
70
Motor capacity
Number of
motor poles
101 (initial
value)
2048
Mitsubishi
Electric Vector
control
dedicated
motor
SF-V5RU (1500 r/
min series)
30
Motor capacity
4
101 (initial
value)
2048
Mitsubishi
Electric
inverter-driven
geared motor
for encoder
feedback
control
GM-DP
Rated motor
current
1800
Motor capacity
4
101 (initial
value)
1024 (initial
value)
GM-DZ
Rated motor
current
1800 (1803)
Motor capacity
4
101 (initial
value)
1024 (initial
value)
Mitsubishi
Electric
standard
efficiency motor
Mitsubishi
Electric high-
efficiency motor
SF-JR
Rated motor
current
0 (initial value) Motor capacity
Number of
motor poles
101 (initial
value)
1024 (initial
value)
SF-JR 4P 1.5 kW or
lower
Rated motor
current
20
Motor capacity
4
101 (initial
value)
1024 (initial
value)
SF-HR
Rated motor
current
40
Motor capacity
Number of
motor poles
101 (initial
value)
1024 (initial
value)
Others
Rated motor
current
0 (3)
Motor capacity
Number of
motor poles
Mitsubishi
Electric
constant-torque
motor
SF-JRCA 4P
Rated motor
current
10
Motor capacity
4
101 (initial
value)
1024 (initial
value)
SF-HRCA
Rated motor
current
50
Motor capacity
Number of
motor poles
101 (initial
value)
1024 (initial
value)
Others
Rated motor
current
10 (13)
Motor capacity
Number of
motor poles
Other
manufacturer's
standard motor
—
Rated motor
current
0 (3)
Motor capacity
Number of
motor poles
Other
manufacturer's
constant-torque
motor
—
Rated motor
current
10 (13)
Motor capacity
Number of
motor poles
Motor
capacity
SF-V5RU
200 V
400 V
Pr.83 (V)
Pr.84 (Hz)
Pr.83 (V)
Pr.84 (Hz)
1.5 kW
188
50
345
50
2.2 kW
188
50
360
50
3.7 kW
190
50
363
50
5.5 kW
165
50
322
50
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...