13. (T) Multi-Function Input Terminal Parameters
13.9 Start signal operation selection
13.9
Start signal operation selection
Operation of the start signal (STF/STR) can be selected.
Select the stopping method (deceleration stop or coasting) at turn-OFF of the start signal.
Use this function to stop a motor with a mechanical brake at turn-OFF of the start signal.
2-wire type (STF signal, STR signal)
• The following figure shows the 2-wire type connection.
• As an initial setting, the forward/reverse rotation signals (STF/STR) acts as both start and stop signals. Either one turned
ON will be enabled, and the operation will follow that signal. The motor will decelerate to a stop when both are turned OFF
(or both are turned ON) during the operation.
• The frequency can be set by inputting 0 to 10 VDC between the speed setting input terminals 2 and 5, or with
Pr.4 to Pr.6
Multi-speed setting (high speed, middle speed, and low speed)
. (For the multi-speed operation, refer to
.)
• By setting
Pr.250
= "1000 to 1100, 8888", the STF signal input becomes the start command and the STR signal input
becomes the forward/reverse command.
NOTE
• By setting
Pr.250
= "0 to 100, 1000 to 1100", the motor will coast to a stop when the start command is turned OFF. (Refer to
• The STF and STR signals are assigned to
Pr.178 STF/DI0 terminal function selection and Pr.179 STR/DI1 terminal
function selection
in the initial status. The STF signal can be assigned to only
Pr.178 STF/DI0 terminal function selection
,
and the STR signal can be assigned to only
Pr.179 STR/DI1 terminal function selection
.
Pr.
Name
Initial value
Setting range
Description
Start signal (STF/STR)
Stop operation
250
G106
Stop selection
9999
0 to 100 s
STF signal: Forward rotation start
STR signal: Reverse rotation start
The motor coasts to a stop after a lapse
of the setting time when the start signal
is turned OFF.
When set to 1000 to 1100 s, the motor
will coast to stop after the time period
calculated by subtracting 1000 s from
the time set in
Pr.250
.
1000 to 1100 s
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
9999
STF signal: Forward rotation start
STR signal: Reverse rotation start
The motor is decelerated to a stop
when the start signal is turned OFF.
8888
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
Forward
rotation start
Reverse
rotation start
STF
ON
Time
STF
STR
SD
Inverter
STR
2-wire type connection example (Pr.250 = "9999")
ON
10
2
5
Output frequency
Forward
rotation
Reverse
rotation
Start signal
Forward/
reverse
signal
STF
ON
Time
2-wire type connection example (Pr.250 = "8888")
STF
STR
SD
Inverter
STR
ON
10
2
5
Output frequency
Forward
rotation
Reverse
rotation
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...