254
11. (H) Protective Function Parameters
11.9 Avoiding machine resonance points (frequency jump)
11.9
Avoiding machine resonance points (frequency
jump)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters allow
resonant frequencies to be jumped.
3-point frequency jump (Pr.31 to Pr.36)
• Up to three areas may be set, with the jump frequencies set to either the top or bottom point of each area.
• The settings of frequency jumps 1A, 2A, 3A are jump points, and operation is performed at these frequencies in the jump
areas.
Example 1) To fix the frequency to 30 Hz in the range of 30 Hz to 35 Hz, set 35 Hz in
Pr.34
and 30 Hz in
Pr.33
.
Example 2) To jump the frequency to 35 Hz in the range of 30 Hz to 35 Hz, set 35 Hz in
Pr.33
and 30 Hz in
Pr.34
.
6-point frequency jump (Pr.552)
• A total of six jump areas can be set by setting the common jump range for the frequencies set in
Pr.31 to Pr.36
.
• When frequency jump ranges overlap, the lower limit of the lower jump range and the upper limit of the upper jump range
are used.
Pr.
Name
Initial value
Setting range
Description
31
H420
Frequency jump 1A
9999
0 to 590 Hz,
9999
1A to 1B, 2A to 2B, 3A to 3B are frequency jumps
9999: Function disabled
32
H421
Frequency jump 1B
33
H422
Frequency jump 2A
34
H423
Frequency jump 2B
35
H424
Frequency jump 3A
36
H425
Frequency jump 3B
552
H429
Frequency jump range
9999
0 to 30 Hz
Set the jump range for the frequency jumps (6-point jump).
9999
3-point jump
Pr.31
Frequency jump
Pr.32
Pr.34
Pr.33
Pr.35
Pr.36
Set frequency after
frequency jump (Hz)
Input set frequency (Hz)
Pr.34
: 35 Hz
Pr.33
: 30 Hz
Pr.33
: 35 Hz
Pr.34
: 30 Hz
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...