12. (M) Item and Output Signal for Monitoring
12.8 Output current detection function
12.8
Output current detection function
If the inverter output current which reaches a specific value is detected, the relative signal is output via an output terminal.
Output current detection (Y12 signal, Pr.150, Pr.151, Pr.166, Pr.167)
• The output current detection function is useful for overtorque detection.
• If the inverter output during inverter running remains higher than the
Pr.150
setting for the time set in
Pr.151
or longer, the
Output current detection (Y12) signal is output from the inverter's open collector or the relay output terminal.
• When the Y12 signal turns ON, the ON state is retained for the time set in
Pr.166
.
• When
Pr.166
= "9999", the ON state is retained until the next start-up of the inverter.
• Setting
Pr.167
= "1" while the Y12 signal is ON does not cause the fault E.CDO. The
Pr.167
setting becomes valid after
the Y12 signal is turned OFF.
• To use the Y12 signal, set "12" (positive logic) or "112" (negative logic) in any parameter from
Pr.190 to Pr.196 (Output
terminal function selection)
to assign the function to the output terminal.
• Use
Pr.167
to select the inverter operation at the time when Y12 signal turns ON, whether the inverter output stops or the
inverter operation continues.
Zero current detection (Y13 signal, Pr.152, Pr.153)
• If the inverter output during inverter running remains higher than the
Pr.152
setting for the time set in
Pr.153
or longer, the
Zero current detection (Y13) signal is output from the inverter's open collector or the relay output terminal.
• Once the Zero current detection (Y13) signal turns ON, the signal is retained ON for at least 0.1 seconds.
Pr.
Name
Initial
value
Setting range
Description
150
M460
Output current detection
level
150%
0% to 400%
Set the level to detect the output current. Consider the value of
the rated inverter current as 100%.
151
M461
Output current detection
signal delay time
0 s
0 to 10 s
Set the timing to detect the output current. Enter the delay time
between the time when the output current reaches the set
current or higher and the time when the Output current
detection (Y12) signal is output.
152
M462
Zero current detection level
5%
0% to 400%
Set the level to detect the zero current. Consider the value of
the inverter rated current as 100%.
153
M463
Zero current detection time
0.5 s
0 to 10 s
Set the time from the time when the output current drops to the
Pr.152
setting or lower to the time when the Zero current
detection (Y13) signal is output.
166
M433
Output current detection
signal retention time
0.1 s
0 to 10 s
Set the retention time period during which the Y12 signal is ON.
9999
The Y12 signal is retained ON. The signal turns OFF at the next
start-up of the inverter.
167
M464
Output current detection
operation selection
0
0, 1, 10, 11
Select the inverter operation at the time when the Y12 signal
and the Y13 signal turn ON.
Pr.167 setting
When the Y12 signal turns ON
When the Y13 signal turns ON
0 (initial value)
Operation continues.
Operation continues.
1
Operation stops by fault (E.CDO).
Operation continues.
10
Operation continues.
Operation stops by fault (E.CDO).
11
Operation stops by fault (E.CDO).
Operation stops by fault (E.CDO).
Time
Pr.150
OFF
ON
OFF
Output current
detection signal
(Y12)
Pr.166
Output current
Pr.166
"9999",
Pr.167
= "0"
Pr.151
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...