203
9. (F) Settings for Acceleration/Deceleration
9.3 Remote setting function
1
2
3
4
5
6
7
8
9
10
9.3
Remote setting function
Even if the operation panel is located away from the enclosure, contact signals can be used to perform continuous variable-
speed operation, without using analog signals.
Remote setting function
• When
Pr.59
≠
"0" (remote setting enabled), the functions of the signals are as shown in the following table.
Main speed
• The main speed used in the remote setting corresponds with each of the following operation modes.
Pr.
Name
Initial
value
Setting
range
Description
RH, RM, RL signal
function
Frequency setting
storage
Deceleration to the
main speed or lower
59
F101
Remote function
selection
0
0
Multi-speed setting
—
Not available
1
Remote setting
Enabled
2
Remote setting
Disabled
3
Remote setting
Disabled
(Turning OFF the STF/STR
signal clears the remotely-
set frequency.)
11
Remote setting
Enabled
Available
12
Remote setting
Disabled
13
Remote setting
Disabled
(Turning OFF the STF/STR
signal clears the remotely-
set frequency.)
Signal name
Function
Description
STF/STR
Forward/Reverse
The inverter accelerates the motor in the forward or reverse direction up to
the main speed or to the frequency stored by the remote setting function.
RH
Acceleration
The set frequency increases according to the
Pr.44
setting.
RM
Deceleration
The set frequency decreases according to the
Pr.45
setting.
RL
Clear
The set frequency is cleared and the main speed is applied.
Terminal 2 (analog signal)
Main speed
The setting of the main speed is used as a base. The main speed is
increased by the RH signal and decreased by the RM signal.
Acceleration
Deceleration
Clear
Inverter
STF
RH
RM
10
2
5
RL
Connection
diagram for remote setting
Forward
rotation
SD
Time
Terminal 2
(main speed)
RM (Deceleration)
RL (Clear)
RH (Acceleration)
STF (Forward)
Cleared by RL
Decreased according to
the
Pr.45
setting
Increased
according to the
Pr.44
setting
ON
ON
ON
ON
Set frequency
(Hz)
Operation mode
Main speed
PU operation mode / NET operation mode
Digital setting
External operation mode / PU/External combined operation mode 2 (
Pr.79
= "4")
Analog input
PU/External combined operation mode 1 (
Pr.79
= "3")
Analog input via terminal 4 (AU signal ON)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...