2. Basic Operation
2.5 Basic operation procedure (PU operation)
1
2
3
4
5
6
7
8
9
10
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.79 Operation mode selection
2.5.2
Setting the frequency with switches (multi-speed
setting)
• Use the RUN key on the operation panel to give a start command.
• Turn ON the RH, RM, or RL signal to give a frequency command (multi-speed setting).
• Set
Pr.79 Operation mode selection
= "4" (External/PU combination operation mode 2).
[Connection diagram]
The following shows the procedure to operate at a low speed (10 Hz).
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Set "4" in
Pr.79
. The PU LED and EXT LED turn ON. (To change the setting, refer to
.)
3.
Setting the frequency
Turn ON the low-speed switch (RL signal).
4.
Start
→
acceleration
→
constant speed
Press the RUN key to start running. The frequency value on the monitor increases according to the setting of
Pr.7
Acceleration time
, and "10.00" (10.00 Hz) appears on the monitor.
5.
Deceleration
→
stop
Press the STOP/RESET key to stop. The frequency value on the monitor decreases according to the setting of
Pr.8
Deceleration time
, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating. Turn OFF the low-speed
switch (RL signal).
NOTE
• The initial value is 60 Hz for terminal RH in Group 1 (50 Hz in Group 2), 30 Hz for terminal RM, and 10 Hz for terminal RL. (To
change the settings, use
Pr.4, Pr.5
, and
Pr.6
, respectively.)
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (
Pr.5
) has the higher priority.
• Up to 15-speed switching operation can be performed.
• Up to two external input terminals are available for the Ethernet model. Use
Pr.178 STF/DI0 terminal function selection
and
Pr.179 STR/DI1 terminal function selection
to assign the functions to terminals DI0 and DI1.
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting)
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.79 Operation mode selection
Pr.178 STF/DI0 terminal function selection
Inverter
High speed
Middle speed
Low speed
SD
RH
RM
RL
Operation panel
Switch
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
RH
RM
RL
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...