28
2. Basic Operation
2.3 Easy setting of the inverter operation mode
2.3
Easy setting of the inverter operation mode
The operation mode suitable for start and speed command combinations can be set easily using
Pr.79 Operation mode
selection
.
The following shows the procedure to operate with the external start command (STF/STR) and the frequency command by
using the operation panel.
Operating procedure
1.
Press the PU/EXT key and MODE key for 0.5 second at the same time.
2.
Turn the setting dial or press the UP/DOWN key until "79-3" (External/PU combined operation mode 1) appears.
(For other settings, refer to the following table.)
3.
Press the SET key to confirm the setting. External/PU combined operation mode 1 (
Pr.79
= "3") is set.
NOTE
• When the user group function is used (
Pr.160
= "1") or the password function is enabled (with
Pr.296 and Pr.297
), the easy
setting is disabled (
Pr.79
is not displayed).
• "ER2" appears if a setting change is attempted during inverter operation. Turn OFF the start command (the RUN key or STF/
STR signal).
• If the MODE key is pressed before pressing the SET key, the easy setting mode is terminated and the operation panel returns
to the monitor mode. If the easy setting is terminated while
Pr.79
= "0 (initial value)", check the inverter operation mode
because the inverter may switch its operation mode between the PU operation mode and the External operation mode.
• Reset by pressing the STOP/RESET key is enabled.
• The following is the frequency commands listed in descending order of priority when "3" is set in
Pr.79
: Multi-speed setting
function (RL/RM/RH/REX signal) > PID control (X14 signal) > terminal 4 analog input (AU signal) > digital input from the
operation panel.
Operation panel indication
Operation method
Operation mode
Start command
Frequency
command
RUN key
Setting dial or UP/
DOWN key
PU operation mode
External
(STF/STR signal)
Analog voltage
input
External operation mode
External
(STF/STR signal)
Setting dial or UP/
DOWN key
External/PU combined operation mode 1
RUN key
Analog voltage
input
External/PU combined operation mode 2
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...