2. Basic Operation
2.6 Basic operation procedure (External operation)
NOTE
• When both the forward rotation start switch (STF signal) and the reverse rotation start switch (STR signal) are turned ON, the
motor cannot be started. If both are turned ON while the inverter is running, the inverter decelerates to a stop.
•
Pr.178 STF/DI0 terminal function selection
must be set to "60" (or
Pr.179 STR/DI1 terminal function selection
must be
set to "61") (initial value).
• When terminal 10 is used, the maximum output frequency may fluctuate in a range of ±6 Hz due to fluctuations in the output
voltage (5 ±0.5 VDC). Use
Pr.125
or
C4 (Pr.903)
to adjust the output frequency at the maximum analog input as required.
(Refer to
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.178 STF/DI0 terminal function selection, Pr.179 STR/DI1 terminal function selection
2.6.4
Changing the frequency (initial value: 60 Hz) at the
maximum voltage input (initial value: 5 V)
• Change the maximum frequency.
The following shows the procedure to change the frequency at 5 V from 60 Hz (initial value) to 50 Hz using a frequency setting
potentiometer for 0 to 5 VDC input. Set 50 Hz in
Pr.125
so that the inverter outputs 50 Hz at 5 V input.
Operating procedure
1.
Selecting the parameter
Turn the setting dial or press the UP/DOWN key until "P.125" (
Pr.125
) appears.
Press the SET key to show the present set value (60.00 Hz).
2.
Changing the maximum frequency
Turn the setting dial or press the UP/DOWN key to change the value to "50.00" (50.00 Hz).
Press the SET key to confirm the setting. "50.00" blinks.
3.
Selecting the mode and the monitor item
Press the MODE key twice to select the monitor mode and to monitor a frequency.
4.
Start
Turn ON the start switch (STF/STR signal), and turn the frequency setting potentiometer clockwise slowly to full.
(Refer to steps 2 and 3 in
The motor is operated at 50 Hz.
NOTE
• To set the frequency at 0 V, use the calibration parameter
C2 (Pr.902)
.
60Hz
(50Hz)
Output frequency
(Hz)
0
0
Frequency setting signal
100%
10V
Initial value
0
5V
Pr.125
Gain
Bias
C2(Pr.902)
C3(Pr.902)
C4(Pr.903)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...