GD310-UL series VFD
Function parameter
-83-
Function
code
Name
Description
Default
value
Modify
Y
RO1, RO2
,
Output frequency
The set
frequency
Detecting
range
T
T
Setting range of P08.25: P08.26
–65535
Setting range of P08.26: 0
–P08.25
P08.27
Set running
time
Pre-set running time of the VFD. When the
accumulative running time achieves the set time, the
multi-function digital output terminals will output the
signal of “running time arrival”.
Setting range: 0
–65535min
0min
○
P08.28
Fault reset
times
Fault reset times: set the automatic fault reset times.
If the reset time exceeds this set value, the VFD will
stop to wait maintenance.
Interval time of automatic fault reset: the interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28: 0
–10
Setting range of P08.29: 0.1
–3600.0s
0
○
P08.29
Interval time of
automatic fault
reset
1.0s
○
P08.30
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the VFD changes as the
load. And it is mainly used to balance the power
when several VFDs drive one load.
Setting range: 0.00
–50.00Hz
0.00Hz
○
P08.31 Motor shifting
Goodrive310-UL supports the shift between two
motors. This function is used to select the shifting
channel.
LED ones: shifting channel
0: terminal shifting; digital terminal is 35
1: MODBUS communication shifting
2: PROFIBUS/CANopen communication shifting
3: Ethernet communication shifting
4: Reserved
0
◎