GD310-UL series VFD
Function parameter
-63-
Function
code
Name
Description
Default
value
Modify
P04.31
Maximum
output voltage
Set the upper and low limit of the output voltage.
Setting range of P04.31: P04.32
–100.0% (the rated
voltage of the motor)
Setting range of P04.32: 0.0%
– P04.31 (the rated
voltage of the motor)
Vmax
Vmin
Vset
t1
t2
T
t1=P04.29
t2=P04.30
100.0%
◎
P04.32
Minimum
output voltage
0.0%
◎
P04.33
Flux
weakening
coefficient at
constant
power
Used to adjust the output voltage of VFD in SVPWM
mode during flux weakening.
Note
: Invalid in constant-torque mode.
Output voltage
Output frequency
(P04.33-1.00)*Vb
out
b
Setting range of P04.33: 1.00
–1.30
1.00
○
P05 Group Input terminals
Function
code
Name
Description
Default
value
Modify
P05.00
HDI input
selection
0: High pulse input. See P05.49
–P05.54
1: Digital input. See P05.09
0
◎
P05.01
S1 terminals
function
selection
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
1
◎
P05.02
S2 terminals
function
selection
4
◎
P05.03
S3 terminals
function
selection
7
◎