GD310-UL series VFD
Peripheral options and parts
-242-
Configuration of the power cable
Double shielded twisted
multi-pair cable
-
Single shielded twisted
Multi-pair cable
-
A double-shielded cable is the best alternative for low-voltage digital signals, but a single-shielded or
unshielded twisted multi-pair cable (Figure b) is also usable. However, for frequency input, always
use a shielded cable.
Note
: Run analog and digital signals in separate cables.
The relay cable needs the cable type with braided metallic screen.
The keypad needs to connect with cables. It is recommended to use the screen cable on complex
electrical magnetic condition.
Do not make any voltage tolerance or insulation resistance tests (for example hi-pot or megger) on
any part of the drive as testing can damage the drive. Every drive has been tested for insulation
between the main circuit and the chassis at the factory. Also, there are voltage-limiting circuits inside
the drive which cut down the testing voltage automatically.
Check the insulation of the input power cable according to local regulations before connecting to the
drive.
Model
Recommended cable size
(mm
2
)
Required torque
(in-lbs)
Wire
connector
(##)
R,S,T; U,V,W;
P1, (+), PB, (-)
PE
R,S,T; U,V,W;
P1, (+); PB, (-)
PE
GD310-0R7G-2-UL
14
12
11
10
Optional
GD310-1R5G-2-UL
12
12
11
10
Required
GD310-2R2G-2-UL
12
12
11
10
Required
GD310-004G-2-UL
8
10
20 or 25 @@
15
Optional
GD310-5R5G-2-UL
8
10
20 or 25 @@
15
Optional
GD310-7R5G-2-UL
6
15
20
8
Required
GD310-011G-2-UL
3
8
25.5
18
Required
GD310-015G-2-UL
3
6
25.5
18
Required
GD310-018G-2-UL
2/0
6
25.5
75
Required
GD310-022G-2-UL
2/0
6
25.5
75
Required
GD310-030G-2-UL
2/0
6
25.5
75
Required
GD310-037G-2-UL
2/0AWG
1AWG
60 or 80 $$
10
Required
GD310-045G-2-UL
1/0 AWG x 2
1 AWG
90
10
Required
GD310-055G-2-UL