GD310-UL series VFD
Fault tracking
-175-
Fault
code
Fault type
Cause
Solution
tE
[20] Motor
autotuning fault
The motor capacity does
not comply with the VFD
capability
The rated parameter of the
motor does not set correctly.
The offset between the
parameters from autotune
and the standard parameter
is huge
Autotune overtime
Change the VFD mode
Set the rated parameter
according to the motor name
plate
Empty the motor load and
re-identify
Check the motor connection and
set the parameter.
Check if the upper limit frequency
is above 2/3 of the rated
frequency.
EEP
[21] EEPROM
operation fault
Error of controlling the write
and read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
PIDE
[22] PID
feedback offline
fault
PID feedback offline
PID feedback source
disappear
Check the PID feedback signal
Check the PID feedback source
bCE
[23] Braking
unit fault
Braking circuit fault or
damage to the braking
pipes
The external braking
resistor is not sufficient
Check the braking unit and,
change new braking pipe
Increase the braking resistor
END
[24] Running
time reached
The actual running time of
the VFD is above the
internal setting running
time.
Ask for the supplier and adjust
the setting running time.
OL3
[25] Electronic
overload
The VFD will report
overload pre-alarm
according to the set value.
Check the load and the overload
pre-alarm point.
PCE
[26] Keypad
communication
fault
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the
keypad and main board.
Check the keypad wires and
ensure whether there is mistake.
Check the environment and avoid
the interference source.
Change the hardware and ask for
service.
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...